  1. J

    Terminating 16mm SWA at 80a switch

    Nasty get off the thread fella and have a beer. Calm yourself down.
  2. J

    Terminating 16mm SWA at 80a switch

    Surely DIY forums are designed to help people who are… you know… learning to do it themselves? No need for comments like this. Thanks to everyone else.
  3. J

    Terminating 16mm SWA at 80a switch

    Okay. That’s exactly what I’ll do. I was planning on terminating the swa into an adaptable box and then running in conduit etc to the switch to keep it hidden, but your plan does look tidier and more simple. 25mm cable it is. Thanks for the help.
  4. J

    Terminating 16mm SWA at 80a switch

    So the distance is roughly 20m. Yes, the current cable in there is T&E as that’s the old cable connected temporarily and I’m replacing that one with the new 3 core SWA. I’ve said 80amp supply as that’s the rating on the main house fuse installed by western power. I don’t believe we’ll be...
  5. J

    Terminating 16mm SWA at 80a switch

    Hi. I’m renovating a project house and have had a new meter installed by western power with smart meter. They also installed some 100amp switches which is helpful. I’ve done something similar to this before, but our main supply for the house comes into the garage, and from the garage, there is...