    Ideal Logic Heat 12 boiler fault

    Still no reply from ideal tech, obviously a bit complicated for them. No other input from anyone ?? as my original post of fault still stands
  2. F

    Ideal Logic Heat 12 boiler fault

    Johntheo5 I have checked SL ( with a DMM and digital scope) and its stable at 240v when it should be but i take your point of adding an additional load to verify. thanks
  3. F

    Ideal Logic Heat 12 boiler fault

    I take your point re the s plan although there are 100k's (or more) of y plan systems operating perfectly ( apart from the slight issue of the valve motor continually using power under certain conditions) I note that you did not mention the pump so i assumne you do not believe that would...
  4. F

    Ideal Logic Heat 12 boiler fault

    existing pump is a Grundfos UPS 15-50 N 130 set at No.3 flow rate
  5. F

    Ideal Logic Heat 12 boiler fault

    double checked (infact about quadzillion checked !!) wiring in JBox for connections to mid pos, valves and room and tank stats, to boiler. all as per spec. It seems to come back to flow when just CH selected, even though pump is powered and running aven though allm rads getting hot ? nd system...
  6. F

    Ideal Logic Heat 12 boiler fault

    Hi again, sorry for delay in posting, away dilalio with 3 port manually opened (to mid point presumably) and just CH selected, boilere beahves as above. That is c on boiler and SL at 240v and pump at 240v and running. blue burner light on for a few secs and then off.. (de selectmanual overide...
  7. F

    Ideal Logic Heat 12 boiler fault

    I have not tried that combination. I will do that later on today and repost. Special thanks to dilalio and madrab for all their useful and knowleable input so far
  8. F

    Ideal Logic Heat 12 boiler fault

    confirmed by a c on display panel
  9. F

    Ideal Logic Heat 12 boiler fault

    Yes SL on boiler strip
  10. F

    Ideal Logic Heat 12 boiler fault

    yes, tested with DMM, constant 240
  11. F

    Ideal Logic Heat 12 boiler fault

    But all rads are getting hot, suggesting that circ pump is ok, and spindle spins freely. Not sure on pump age the boiler is shutting down within couple of secs. Not even ideal can get a boiler to raise temp that quickly !
  12. F

    Ideal Logic Heat 12 boiler fault

    removed cyl stat which is a basic mechanical 3 contact type. common, norm closed and norm open, this all fine when tested
  13. F

    Ideal Logic Heat 12 boiler fault

    Madrab As in my or post, all rads get hot when CH and DHW selected sytem DOES shut down when cylinder stat satisfied
  14. F

    Ideal Logic Heat 12 boiler fault

    existing system, new build from 12 years ago. As per original installation. There is no mag filter madrab - I totally agree something not right. I cannot get my head around there being a call ( c ) on boiler display whether on HW only or CH, and the boiler somehow differentiating c for CH only...
  15. F

    Ideal Logic Heat 12 boiler fault

    Hi. Tks for that. The HW off 240v from timer is connected to grey mid pos valve and has 240v when no HW demand
  16. F

    Ideal Logic Heat 12 boiler fault

    It's a corgi, Yes taken off control head. Valve moving fine as is control head and providing correct switched SL output on orange dependent on motor position. Confusing
  17. F

    Ideal Logic Heat 12 boiler fault

    Hi. Perfect info SL stays at 240, also confirmed by c on boiler even though burner will not light. I have checked 3 port, orange only live when both grey and white live. Confirmed this out of cct, by checking continuity and manually moving valve
  18. F

    Ideal Logic Heat 12 boiler fault

    Thanks for reply. Pump is from boiler When just CH selected, pump switches on and is circulating, with 0 changing to c after about 10s. At the same time c appears SL goes to 240v. Blue light comes on for a few secs , then off. If then HW selected, then boiler lights, pumps stays on, and flow...
  19. F

    Ideal Logic Heat 12 boiler fault

    dilaio. Thanks but as stated flow is fine around CH circuit, pump switches on as soon as call for CH