  1. S

    ring main keeps tripping

    What kit would that be ? and where do you charge £50 hour? I'm in Manchester.
  2. S

    ring main keeps tripping

    Nothing to be embarrassed about i charge £15 hour client was not willing to pay for the hours needed to find the fault! Yes if we spent more time eventually the fault would of been found. at one point i was willing to find this fault for nothing because it was doing my nut in! But it was...
  3. S

    ring main keeps tripping

    Nothing pluged in the circuit, stays on for a half an hour, trips, some time times after its trip and you try to switch it back on it goes pop and then you try again and it stays up for a versus time then, trips .Disconnected all but two legs on the ring still tripping. cable coming from the C.U...
  4. S

    ring main keeps tripping

    Ring main keeps tripping,found three sockets metal back boxes with condensation in them which is dried out, ring trip again. Took the face off ever socket on the ring main all wiring correct and sockets dry, ring keeps tripping. we then removed the rest of the legs in the ring except two...
  5. S

    ring main with half the ring with no neutral

    went to a friends house who said that some sockets in the kitchen and up stairs landing and bed rooms sockets not working. well started in the kitchen with the two not working to find they tested 6v and the same upstairs which brought me to think there is a neutral down some where. well after...
  6. S

    creda storage heater

    5 storage heaters in a flat the hallway one not getting hot, power to the unit but no heat. checked the timer and turn it on manually power came on to the unit took the front cover off where the controllers are. power there at the controller still not getting hot. could the controller eliment be...
  7. S

    two down lights keep blowing

    in a hallway there are 5 down holegen lights two of which keep blowing on a single poll switch. do they need rewiring?
  8. S

    storage heaters

    thanks you guys found the problem! bs 5424 breaker the coil is gone and found out that this device belongs to the suppler. so i will let them fix it. but just want to find out way there was no power to this board. i opened this device removing the mains fuse first, so that everything was dead...
  9. S

    Problem with storage heaters

    thanks you guys found the problem! bs 5424 breaker the coil is gone and found out that this device belongs to the suppler. so i will let them fix it. but just want to find out way there was no power to this board. i opened this device removing the mains fuse first, so that everything was dead...
  10. S

    Problem with storage heaters

    5 storage units in the house thats suppose to turn on at 10:30pm. when i checked the 5 units are wired to its own board with 100amps breaker.wired to a 250v breaker on the norweb side power coming into the breaker no power going out to the board. is problem with the suppliers side ? thanks you guys
  11. S

    Changing a old board for new one

    guys rome wasnt built in a day.how else am i to get experience, how did the expert electrician get to were he is today! not saying to his self i better not try that i'll leave it to the expert. I am not saying you guys are wrong in what you are tell me.otherwise i wouldn't come in to this forum...
  12. S

    Changing a old board for new one

    hi guys its me again, well this should be straight forward i guess. iam going to take the old board off three bed room house.which has the old style fuse's,rewire.two red,one white,and one yellow. so basically tape and number each wire from the fuse it came from.and put back everthing i took...
  13. S

    Charge

    How much should a person charge for installing a shower?
  14. S

    Lighting upstairs in a pub can't find the board.

    thanks guys i'am glad everone thinks it funny but what about when you guys were apprentice's you to didn't know f__k all! i'am learning yes, so please try to be understanding. i found the board for the upstairs one side of the flats lights are fine.there are three rooms/hallway and toilet that...
  15. S

    Lighting upstairs in a pub can't find the board.

    Found the board yeaaa, its on the second floor of the pub one side of the flat is fine the Light are good but when you go to were the funtion room use to be they have made three rooms out of it. two more rooms are next to the three new ones.I went up into the loft and found two twin and earths...
  16. S

    Lighting upstairs in a pub can't find the board.

    big pub with 5 bed rooms. the main board for the pub is down stairs would them lights upstairs be on the board down stairs or would there be a board for upstair,be some were? and puting in a shower would i be puting that on the same board upstairs or get it from the main board in the pub?
  17. S

    wiring falt on a ring main

    thanks to you guys job done ! took off all the sockets fronts and the juction box. check all the wire,s one by one and when i got to the last one which was in the kitchen the red wire/s in the sockets was lose.Thanks again. The Dog wuff wuff
  18. S

    wiring falt on a ring main

    thanks John will let u know today how it went!
  19. S

    wiring falt on a ring main

    Right 3 dubble sockets in the living room,2 dubble sockets and a junction box feeding the washer and a pull swicth on the wall. were do i begin my test? and how.
  20. S

    wiring falt on a ring main

    between live and nutral