  1. A

    BAXI COMBI INSTANT 105E

    Hi Mick, I need to be able to check the condition of the diaphragms, usually i just slip a pipe onto the outlet tap and the boiler drains, I don't need to drain the radiators, just the boiler, to remove the pressure from the diaphragm housings so that I can unscrew them without water pouring...
  2. A

    BAXI COMBI INSTANT 105E

    Can anyone help - I have a problem with dhw but I can't seem to drain the system to be able to take a look at the diaphragms etc, i have switched off the mains water and power, I only get about a pint of water from the drainining point on the boiler - any ideas?
  3. A

    Baxi Combi Instant 105e - no DHW problem:

    Post Subject: Re: Replacement PCB fitted. Forgot to put the above into the body of the text ! Bit more information: This boiler basically unused for the last 9 months, guy in the middle of a Divorce, living in the property on his own, just let it lie, the house, the boiler...
  4. A

    Baxi Combi Instant 105e - no DHW problem:

    HOT TAP TO ON> PANEL LED'S ON>BOILER LIGHTS - YEEEEEHA - DHW RESTORED !! Many thank's all for all your kind assistance. Phew ! :-) Keith.
  5. A

    Baxi Combi Instant 105e - no DHW problem:

    Fitted new motor head to the diverter valve and.... same problem, no DHW or boiler startup - (no laughing at the back there:-) Same supplier has a pcb in stock and has kindly offered to give me credit against the motor head if that's not the problem, decided I may as well leave it on as...
  6. A

    Baxi Combi Instant 105e - no DHW problem:

    Points taken - my thoughts: I can replace the motor today for £17 from local supplier. Baxi troubleshooting guide clearly shows that if voltage present at pcb then motor is faulty. Having said that, there may be voltage present, but something else on the pcb has failed and it's not...
  7. A

    Baxi Combi Instant 105e - no DHW problem:

    As per the Baxi troubleshooting guide I checked the voltage between pins 1 & 3 on the A8 block - 244 volt there which pretty much suggests that the diverter valve motor head has gone as the cable loks fine. Will replace that and let u guys know if it fixes the problem. Very many thank's...
  8. A

    Baxi Combi Instant 105e - no DHW problem:

    Wires correct - baxpoti. Diaphragm and both microswitches replaced and microswitch can be heard to click when DHW requested. Just downloaded the Manual from Partsarena (ta for that!!). In the troubleshooting section I can see voltages mentioned on pinouts on the PCB I'm going to check...
  9. A

    Baxi Combi Instant 105e - no DHW problem:

    Motor head appears completely dead - no movement / vibration whatsoever when DHW demanded. I guess the next thing is to confirm that 240v is getting to the motor head, any idea what pins - I think there are 3 contacts ? No manual - have u got one to pass on? ! Keith.
  10. A

    Baxi Combi Instant 105e - no DHW problem:

    Hi Dave, the vertical pin on the valve will move with a bit of finger effort, it feels ok. to be honest, nice and smooth, but as u say with some resistance. Keith.
  11. A

    Baxi Combi Instant 105e - no DHW problem:

    That didn't read to well what I meant to say was that when the motor head is removed, the brass pin standing upright on the valve can be depressed, with some effort.
  12. A

    Baxi Combi Instant 105e - no DHW problem:

    Hi all, swapped the sensors and also checked for open circuit - both ok, and same problem with no DHW. Whipped the motor head off the preheat diverter and see if the motor is moving the pin - nope nothing happening there when DHW requested. The brass pin is finger moveable downward with...
  13. A

    Baxi Combi Instant 105e - no DHW problem:

    Will swap the sensors tonight and let u know how I get on Thank's for your advice everybody - very appreciated. Keith.
  14. A

    Baxi Combi Instant 105e - no DHW problem:

    Thank's again guys I'll replace the PCB and let u know how I get on. Keith.
  15. A

    Baxi Combi Instant 105e - no DHW problem:

    Damn that was quick ! I did think that this was probably the case - no way it could be the 247394 temp sensor ? Ta, Keith.
  16. A

    Baxi Combi Instant 105e - no DHW problem:

    Hi, can anyone assist with my problem ? Combi Baxi Instant 105e - no DHW problem. Slowly getting worse over the last month or so and now no DHW at all. Good radiator heat all round. When turning hot tap DHW pin clearly moves out. no leds light on control panel (power led on) -...