    Increasing lighting circuit MCB ampage

    This is the e mail response from Endon "This is a common characteristic of this type of transformer; a toroid. Usually the electrician sorts them out so we don’t put advice in the fitting instructions. In 99% of the cases a type C breaker sorts out the problem, a type D which I...
  2. S

    Increasing lighting circuit MCB ampage

    It surprised me and I would have expected a warning in the fitting instructions. However the technical department at Endon advised me of this. Has any electrician out there fitted a light fitting from Endon with 12 x 20 watt low voltage halogens and a transformer without the need to replace the...
  3. S

    Increasing lighting circuit MCB ampage

    The Cat C MCB seems to be coping now, it has only tripped out twice. If it trips more frequently I will try the dimmer suggestion. If that fails maybe I'll move house. Thanks for everyone's help.
  4. S

    Potterton PrimaF Boiler keeps tripping out

    My Potterton boiler is constantly tripping out, there is sometimes a spark arcing from the ignition wire where it is nicked, could this be the problem and if so would a covering of insulating tape suffice.
  5. S

    Increasing lighting circuit MCB ampage

    [/url] Having viewed the IQ dimmer through the above link this seems to be a logical solution. Will wait and see what bernardgreen's contact says then tackle the issue. Thanks.
  6. S

    Increasing lighting circuit MCB ampage

    It is round and foil wrapped.
  7. S

    Increasing lighting circuit MCB ampage

    Only trips at switch on, there is only one switch.
  8. S

    Increasing lighting circuit MCB ampage

    The fitting is an Endon 704 - 12SC with 12 x 20 watt halogens and a transformer built into the ceiling rose. It is certainly a domestic fitting.
  9. S

    Increasing lighting circuit MCB ampage

    Thought you might say that, won't go any further until an electrician has tested system. Thanks for your advice. Do you know where I can buy hair straighteners!?( Just kidding)
  10. S

    Increasing lighting circuit MCB ampage

    Acted before reading further posts, still alive! Have replaced Hager B6 MCB with Hager C6 MCB as Endon advise that the transformer causes high in rush current and requires either Cat C or Cat D. With Cat C in place there is less tripping but still some. Will therefore try Cat D.
  11. S

    Increasing lighting circuit MCB ampage

    Managed to speak to tecnical dept at Endon, apparently it needs a type c MCB due to initial surge. Thanks for help.
  12. S

    Increasing lighting circuit MCB ampage

    The MCB make is Hager, from recollection it does not just slot in, it is attached by screws. The Circuit Board was installed in Jan 1994 when house was rewired. Does this tell you enough or should I wait until I get home?
  13. S

    Increasing lighting circuit MCB ampage

    Sorry to be vague but I am not at home at the moment, the cable seems to be standard domestic lighting cable, twin & earth in grey sheath approx 1 cm wide.
  14. S

    Increasing lighting circuit MCB ampage

    I have just replaced a ceiling light with an Endon fitting, this fitting has 12 x 20 watt halogen bulbs and a built in transformer. The light works most of the time but occassionally the 5 amp MCB trips out (even when this is the only operating light on the circuit) . Is it safe to uprate this...