  1. D

    Underfloor Heating

    The thermostat is only rated at 16 amps, the way you are suggesting was how I was goin to do it originally but I was concerned that the thermostat rating would be exceded??? Would the DP switch be 20A ??? Thanks
  2. D

    Underfloor Heating

    Thanks. you have n't confused me, youve actually made my decision for me. 20a mcb feeding 20a 2 pole contacter ,rcd protected. Cheers
  3. D

    Underfloor Heating

    Thankyou...I think your probably right...I'm gonna go the contactor route, cover all the bases that way. Unless anyone thinks this is OTT Thanks
  4. D

    Underfloor Heating

    Sorry I mean 4.25x4.25..Its underfloor matting and the manufacturers are quoting 200 watts per sq metre output...is this enough info? Thanks
  5. D

    Underfloor Heating

    Hi I am installing Underfloor Heating approx 18m2 @200w/m. I have a dedicated feed available(rcd protected) From The CU. Can someone please advise 1/ Do I need an FCU between the feed from the CU and the thermostat? 2/ If so what size fuse should I use? 3/ what size mcb at the CU...