    Boiler runs but pump doesn't - central heating system.

    Thought anyone watching this post would be interested to learn the cause of the problem - a nail had pierced a neutral supply cable in the loft space, and amazingly, the house in qustion was built in 1992 ! Point to note - just because wiring has been in place for some time, don't assume it...
  2. X

    Boiler runs but pump doesn't - central heating system.

    Many thanks for your thoughts guys - I'm on the right track now looking for the neutral path. Best regards.
  3. X

    Boiler runs but pump doesn't - central heating system.

    Yep - runs fine. I'm pretty sure the problem lies in there not being a neutral return but can't seem to figure out the return path ! Is there a possibility the return could be via the room stat and the neutral could be lifted in there for some reason ?
  4. X

    Boiler runs but pump doesn't - central heating system.

    Thanks for looking in Corgiman - having checked more in the connection box where the pump, valve and cylinder are located, all of the terminals on the barrier strip (with the exception of earth of course) read live.
  5. X

    Boiler runs but pump doesn't - central heating system.

    Hi - boiler is Myson Orion, valve is Horsemann Z322.
  6. X

    Boiler runs but pump doesn't - central heating system.

    Hi all - hope someone may have had this problem before. Central heating with 3 way motorized valve - problem is that on any setting, ie heating on, water on or both, boiler will fire up assuming thermostats are turned up, however pump will not - consequently cut out occurs on boiler within a few...