Changed pump now overflowing!

Joined
13 Feb 2010
Messages
7
Reaction score
0
Location
Birmingham
Country
United Kingdom
my 10 year old grundfos 15 50 central heating pump has got noisy recently so i changed if for a new one today and all went rather well! I put the heating on and the house warmed up really quickly.
i could hear running water so went into the loft to investigate and noticed hot water running out through a vent pipe into the top of the central heating tank in the loft. each time i put the boiler on for either the heating or to heat some water for the immersion tank hot water overflows. the tank in the loft is hot too touch and full of hot water.

i have tried turning down the thermostat on the boiler with no effect.
the new grundfos 15 50 is on the lowest setting (1)
both valves that i closed to change the pump have been opened up again.
my boiler is a glow worm.

I have taken a picture which can be seen here - http://www.diynot.com/network/medic999/albums/

my knowledge on this sort of thing is very limited so would appreciate any advice (i am quite good at medicine so would be happy to give my opinion on any coughs or colds you may have)!
 
Blockage somewhere? Is there an air seperator fitted? (Round 'can' type thing, before the pump.)

not that i can see.

if i close the gate valve that comes from the tank in the loft into the pipework the water stops overflowing the other way back into the top of the tank in the loft
 
check where cold feed enters system with a magnet, if it sticks you have a blockage
 