I hope one of you kind people out there can help me .
The pipes start to hammer after half an hour of CH or HW or both.
overheat on the boiler then needs to be reset
pump is working
midpoint actuator is moving
engineer changed pcb problem still occuring
its a baxi solo 3 50 pf
help please
thankyou all for your help here is a bit more detail
changed water tank thermostat
actuator changed
have not yet changed boiler thermistor
have not changed room thermostat
I put the boiler on and after half an hour the pump stopped working
the boiler was still going and started to hammer
i then turned off boiler manually
pump did not come on to disperse heat
suggestions please