room stat not calling for heat

Joined
25 Feb 2011
Messages
1
Reaction score
0
Location
Surrey
Country
United Kingdom
hello all
i have a problem with a room stat in my house.Set say at 20 ,all is well.Once temp is reached the boiler turns itself off.As the temp in the house falls the stat does not call for heat at all,the boiler stays off.There is a 3 core cable at the stat,and i realise that 1 of these cores is not connected right at the junction box .Please,can anybody enlighten me .
It is a very old glo-worm 45 back boiler,gravity hot water,pumped c/h.
with a honeywell v4073A 1039mid position5 wire motorised valve, cyl stat
honeywell L641A1039 prog ,potterton EP2002 &pump.
Thank you
 
Are you any good with a multimeter??

First would be to check for continuity and open line while amking and breaking the switch (or 240v - 0v when making and breaking the switch)

THis will then rule out the RS.
 
can also do it dead with electricity off - a lot safer - test for cont when switch is made
 