I've checked the wiring connections and all seem tight. I only swapped wire for wire when replacing the valve do am pretty confident that that'd right.
Kev, more help please if you're around!!!
My system is not performing correctly. last night everything was working ok - hot water and hot radiators.
today i come home from work to cold radiators but hot water. the boiler is firing for a couple of minutes then stopping every half hour or...
the boiler just kicked back in (for any unkown reason...)
so i sprinted up the stairs and undid the screw on the pump, got loads of air out and from the vent as well and the boiler is still running... :lol: :lol: :lol: :lol:
thanks very much for all your help. very much appreciated. will...
cheers for that kev. I have bled both points until water runs continuously but still have nothing.
Where would you go next?? Apart from the pub which is where I feel like going... :lol:
kev - when i select either hw or ch then the mid-position valve reacts in the required manner.
pedanticvindictiveman - damn fine idea.....only if they didn't charge so much I would!!!
seco - I have 240V on the orange when demand is called for.
Hi guys, first-time poster here!!!!
I have a problem with system listed above. The boiler was working fine until very recently when the central heating stopped working, although the hot water worked fine. I searched various places on here and self-diagnosed the problem as the mid-position...