    Biasi Garda HE - Full sequence Ignition device problem?

    All fixed. The key was that there was no gas flow and no spark. This lead to the culprit being the air pressure sensor. However the solution was much simpler :oops: In putting back the covers and shelves in the boiler cupboard one of the pressure testing caps had come off :(...
  2. B

    Biasi Garda HE - Full sequence Ignition device problem?

    Many thanks, I cannot see the gland you refer to on the parts list or exploded diagram? Does it mean replaceing the hwole unit? The old flow switch did have condensate in it so I replaced that as well. The switch works correctly and the plunger operates well too. Surely if that was the...
  3. B

    Biasi Garda HE - Full sequence Ignition device problem?

    I think I mat have the answer to this but thought I would check here anyway. My Garda started leaking from the primary circuit flow switch plunger. Simple fix was to replace the diapram. All worked fine, no leaks and boiler started well. However having raplced all the panels the...
  4. B

    PCB replacement

    I have just had the same issue. The PCB in question was the Honeywell Full Sequence ignition device. One of the relays near the 7 pin connector has burnt out and fried the PCB. Been doing some research on the web and seen a few with this problem. It may explain why there are two variants...