Recent content by Booie

  1. B

    Issue with Mid Position Actuator

    Well.. I've just put it all back together, but thought I'd leave the blue wire we switched from 2 to 1 and see what happened. Much to my amazement, it seems to be working perfectly now. Sorry for messing you guys around and thank you very much for putting up with me and helping me out.
  2. B

    Issue with Mid Position Actuator

    Looks like i'm going to have to get a pro in on this as it seems like its in a real mess. Brilliant :roll: Thanks for all the help guys...I'll let you know if/when I ever get to a solution.
  3. B

    Issue with Mid Position Actuator

    Hi, sorry missus stole the PC. Erm, its def 12v, my meter is right as it reads 230v out of sockets. Could the blue wires in the wiring centre be muddled or something? Very strange...I know...
  4. B

    Issue with Mid Position Actuator

    Ok, I've done that. The Blue Wire now reads 12V at the Wire Centre, with HW/CH off at programmer.
  5. B

    Issue with Mid Position Actuator

    I'm sorry, but the Blue's are in 1 and 4 already, arn't they? If I number them like the image below, could you let me know which wire is incorrect then? Sorry again <- Novice
  6. B

    Issue with Mid Position Actuator

    Heres the programmers wiring:
  7. B

    Issue with Mid Position Actuator

    As far as I can tell, there's no voltage on any of those three terminals.
  8. B

    Issue with Mid Position Actuator

    Got my multi meter now. Sorry for the delay, toolbox wasn't at home. What do I need to test?
  9. B

    Issue with Mid Position Actuator

    Sorry, my mistake with the last photographs. Plumbing isn't really my strong point, especially when it comes to what each of the parts are called. I don't have the tools at the moment to test if the Grey wire is live, so hopefully the issue can be spotted from the images below, if not, I'll...
  10. B

    Issue with Mid Position Actuator

    I hope these pictures are good enough (And they help)
  11. B

    Issue with Mid Position Actuator

    So what would you suggest? Get the entire system looked at by someone? An electrian or a plumber? As for it being upside down, I'm pretty sure that's just the awful angle I had to get my camera in to take the picture =)
  12. B

    Issue with Mid Position Actuator

    Hi there, I've been having some issues with my Hot Water and Central Heating for a while now and we've had a plumber out twice who seems to fix the problem we were having at the time but then another issue arises soon later. So I was wondering if anyone could advise me to what the actual...