    Johntheo5 replied to the thread UFH running too hot.
    The dT is the difference between the UFH flow and return manifolds, normally temperature gauges on both manifilds,
  • J
    Johntheo5 replied to the thread UFH running too hot.
    Any idea of the manifold flow and return temps?, can then calculate exactly the UFH/boiler output. Total lool(s) flowrate...
  • J
    If your boiler is the one shown in these MIs then it doesn't mention any adjustment, it just looks like a simple, maybe spring loaded...
    • 1762125377207.png
  • J
    It certainly will/should be reading accurately but that doesn't mean that the actual rads return are at the same temperature IF the ABV...
  • J
    Does the boiler display flow and return temperatures or are you measuring the return (and flow) at the boiler. The MIs for this boiler...
  • J
    Johntheo5 replied to the thread UFH running too hot.
    When the UFH is only on, (no rads) are the loop flowrates the same as when both UFH & rads are both on? How many UFH loops and total...
  • J
    Johntheo5 replied to the thread Hot Water Running Out.
    Ring your plumber and ask him does your cylinder have a pump with secondary return. You also stated your usage is exactly the same as...
  • J
    Johntheo5 replied to the thread Bypass valve.
    Could be sludge partially blocking the boiler HEX and pump impeller or/and pipework, system may require a power/chemical wash,was the...
  • J
    Johntheo5 replied to the thread Bypass valve.
    Circulation flow seems a problem, you can see below that if 75C is the flow temperature then the return must ba as low as 25C with a...
    • 1762011028393.png
  • J
    Johntheo5 replied to the thread Bypass valve.
    Gas consumption, 067023.71 minus 067023.635, 0.075m3= 0.075*11, 0.825kWh= 0.825*60/3, 16.5kWh, at 90% boiler efficiency = boiler output...
  • J
    Johntheo5 replied to the thread Bypass valve.
    No need for a engineer. Just your smart phone, as stated above just take a photo of your house gas meter readings exactly 3 minutes...
  • J
    Johntheo5 replied to the thread Bypass valve.
    So, its running continuously after a few cycles?, if so the outputting ~ 18kW. The two thermocouples show a rad output of ~ 17.2% of...
  • J
    Johntheo5 replied to the thread Bypass valve.
    Not sure where I thought I saw this but your model certainly doesn't seem to have one so better from a trouble shooting point of view...
  • J
    Johntheo5 replied to the thread Bypass valve.
    That boiler has a internal ABV (automatic bypass valve), If it took an hour for the boiler outle to feel like 70C then something...
  • J
    I would get a isolating valve and pressure gauge installed where that black plug is and leave it permanently installed, as a first step.