Looking at the sensor readings you can see the CH switched live is on and turns off when we turn the heating off, the boiler just doesn't seem to be doing anything with it.
I'm starting to think that too. I haven't no as the hive was fitted as our old thermostat broke (wireless ideal touch which almost blew itself up) so have no means to test.
I suspected the threeway valve was faulty but the fact it moves to all 3 positions when in vent mode leaves me a bit puzzled.
Thanks for your response.
Yes that's correct I have removed the loop from the room stat / timer plug and wired from connection 1 & 3 on the receiver.
When turning the heating on the receivers green light comes on and I can hear the unit click, checking the volatge I get 230v at the indicated...
Hi all,
Hope someone can help me out here.
I have just fitted a Hive thermostat to our Ideal Vogue C32 Gen 2 boiler. Initially the thermostat worked fine for around a day, the heating switched on and off as per the schedule as it should.
After a day the heating has stopped coming on. I have...