sorry been out all day, can someone post a pic of the boxes i need please, i want to go thru the back into wall if poss, i can run an earth from small CU rail to banjo.
Thanks
many thanks for your help, thats what i will do then.
i have a couple of spare locknuts so i can sandwich the banjo.
cheers, just waiting for the rain to stop so i can crack on!
thanks thats what i originally planned, just concerned about the T&E coming out the bottom of the box and into the wall (in the open unprotected). would it be better to go thru the back of the box thru the walls and seal the box against the wall?
Do i need special glands for the flat T&E or...
thanks for your help, but im getting more confused:
this is what i have:
6mm 3core SWA
6mm T&E
IP66 box x2
Garage CU
28mm Timber Wall in cabin
Brick cavity house wall
Hows best?
Many Many Thanks
will be from main cu to the floor then along the bottom of wall all in trunking.
also whats best IYHO
swa thru the cabin wall then gland in small cu
swa thru the cabin wall then gland in ip66 box next to small cu, long tail into small cu
swa gland in ip66 box on outside cabin wall...
ok thanks, thinking about it ill stick to 20a as the cabin CU is 16a/6a
Is it ok to joint 6mm 3core SWA to 6mm T&E in a IP66 Junction Box, the earth size would be different using the 3rd core of SWA and the earth of the T&E, is this ok?
Many Thanks
starting this project now, is it ok to put an ip66 junction box on the side of the cabin gland the swa into it and take the tails thru the back of the box straight thru the wall into back of CU, basicly drill a hole thru the back of junction box - wall - CU with silicone between?
Oh and i...
I want to fit a night latch to my log cabin and wondered if its possible to use one on an outward opening door?
Are they all adjustable if not what do i need to look out for
thanks
Been talking to some friends about my upcoming outbuilding wiring project and one told me they buried SWA just 8inches under lawn and put a scaffold board on top of it to stop spades etc hitting it :o they also said their electrician said this was fine, is that so?