Recent content by morg

  1. M

    LED Shower Niche

    Great thanks for all the help Totally agree with you the kit is poor on the electrical side, Wagobox is a good idea, cheers Yeah its a bit expensive and bulky that vented enclosure, I think its best to use a small access panel instead as we have other equipment i.e the bathroom fan / vent...
  2. M

    LED Shower Niche

    Hi, I didn't ask about the driver location. But as you say the meanwell datasheet states "Cooling by free air convection" That said I guess that means all LED drivers shouldn't be stuffed in the ceiling void, but I bet most are installed in the ceiling void or some other air tight location...
  3. M

    LED Shower Niche

    Hi, I've just had an email back from Thermopanel, They are saying the LED is rated IP67.
  4. M

    LED Shower Niche

    Hi, still unsure how to proceed with the niche, If we get a better LED driver replacement (i.e. a decent one from TLC with T+E connections / 12v connections so the electrician can terminate properly) With the above 'upgraded' and however, does the 12v LED (unknown IP rating) itself still pose...
  5. M

    LED Shower Niche

    Ah my mistake thanks for correcting,
  6. M

    Any advice welcome

    vibration / air compressor?
  7. M

    LED Shower Niche

    It appears Thermopanel is a reputable company, like I said I think the niche itself is good quality and looks good to be fair, but thermopanel don't advertise LED niches on their website, so I'm guessing a third party has added the poor quality LEDs.
  8. M

    LED Shower Niche

    The bottom pic... Yes that's light shining through to show the gaps on the middle shelf I guess either they purposely left gaps for drainage or it's poor welding.
  9. M

    LED Shower Niche

    Hi, The LED driver is going to be outside the bathroom / zones somewhere, probably in a access panel with the bathroom downlight driver also. Yes that's one of the 12v cables to LED. Good point on the unsheathed 240v cables, its all crap / dangerous. Shame as the niche itself is good...
  10. M

    LED Shower Niche

    Thanks for the help, Yeah I thought it was a bit concerning with the cables rubbing against the metal, wasn't cheap either at £150, So basically it's not fit for purpose, Looks like the LED should be rated to a minimum of IP44 (zone 1) or better IP65, Thanks
  11. M

    LED Shower Niche

    Hi all, Looking for some guidance with a stainless steel niche I've recently bought. Have some concerns about this kit, it is branded (Thermopanel) and bought from a reputable company (wetroom store) What I noticed is the middle shelf, the shelf drain is near the 12v cable entry, water is...
  12. M

    Pressure reducing valve

    Hi, currently no problems as no plumbing exists :ROFLMAO: I'm still renovating, so basically all plumbing is currently stripped back to internal stopcock, hence the plan of what is best to fit now rather than later, Not planning on oil boiler, just the basics really 24kw gas boiler, mixer...
  13. M

    Pressure reducing valve

    Thank you both for the advice and info, that's reassuring and saves time/money not fitting one if not essential (y)(y) Good idea just fitting a pressure gauge though :idea: Maybe on the boiler filling loop? (think I've seen loops with 2 x gauges) As not much room near stopcock / DCV, Thanks again
  14. M

    Pressure reducing valve

    Hi, Would it be good practice to fit a PRV even if the mains pressure was normal i.e. 2 - 3 bar? More of a preventive measure, I assume pressure from the kerb mains could potentially spike/raise? Thanks for any help
  15. M

    Finding a hidden water leak

    Could it be electric shower / mixers weeping internal valves which isn't obvious i. e a long/intermittent drip could go unnoticed Can stopcocks weep in the open position (from the gland nut / turn shaft) :unsure: