Hello everyone!Before everything , I hope my question can fit within the topics considered in this forum.I'm newly qualified plumber (not CORGI) and just started a job which supposed to be something like a plumber's mate.It turnes out though , as I will have a chance of taking a lot more...
Yes,guys,no CH,no HW,no pump or fan running - nothing.I try to be as precise as I possibly can - I turn the boiler on from the spur.The green light is lit.No spark , no noise - nothing.It is set for both CH&HW.Tried also only for CH - the same.The red reset pin stays pushed in.When run the hot...
There is also a leakage from a gate valve on the water main.This has probably caused the pressure drop I notised.I refilled to 1.5 bar - same thing.Previously pressure has been down to 0 with the boiler still working so I don't think this was the fault but just to mention that I tried it.
No,the little red button seems to be tucked in,tried to push it but it doesn't move.The green light is on.Very little noise like just power running from the boiler,nothing else.No fan,no pump...?!Cheers!
Hi to all!The subject pretty much says everything.I haven't tried anything yet apart some heavy thinking and taking off the front cover of the combi.doesn't help... :) When I turn the HW tap in the kitchen(closest to the boiler) I hear switching noise which I suppose is the microswitch obviously...