Any advice on the best/easiest way to add Sentinel X500 to a sealed CH system?
I have noted this option:
http://www.eezyfill.com/Information_Eezyfill.htm
Any advice appreciated, cheers n Merry Christmas
Pressure is dropping on my Glowworm Ultracom 24cxi so I need to top it up. Have already looked at advice/videos online and most show 2 large blue filling taps and a disconector with a green collar underneath. However, my boiler doesn't have either. It does have 2 grey taps which I have already...
I managed to find a drain cock and my expansion vessel is now repressurised to 1 bar. However, the PRV pipe is still dripping so the valve must need replacing, thanks again
Thanks for the continuing help.
As per the re-pressurizing instructions do you have any idea where I would find a suitable drain cock as I cant find one?
Yes the PRV pipe is dripping as I tied a bag to it to catch the water....
So does this mean the PRV is defective which is causing this?
If so is it an easy job to replace the valve??
The expansion vessel is up to 3 bar, the correct pressure
My Ideal FF350 Fanned Flued Boiler is losing pressure at the rate of 1 bar in 12 hours.
Anyone got any suggestions as where to start? :?
All radiator valves seem ok, no wet carpet patches to date.
Thanks