Tony,
Thank you for your post. If the original installer has bent me over once before and is unlikely to fix it without charging me anyway it is probably best to just have someone else do it.
Do you have any idea how much it would cost to run the pipe around the exterior wall to the...
The guy checked the hob flames and they didn't show any effect when the boiled fired up. I remember because he said at the time if they did he would have to disconnect it.
Does that make it At Risk or Not up to current standards then?
I don't follow. Only the boiler was replace and attached to the existing pipes. since the pipes were installed the bathroom has been tiled so I would think it would be a big job.
There is an external wall that can connect the meter and the boiler. I wasn't sure if you could have it running against a wall or if it had to be covered?
Any idea how much it would cost to have that done?
I had a Valliant ECOTEC 831 boiler installed 2 years ago. At the 1 year service the boiler man said the appliance was under gassed. The pressure at the meter was 20.4mb but when all appliances (I also have a gas hob) are in operation the pressure at the boiler is 14mb.
The boiler guy put...