  1. V

    Cold Rad

    yep! you are all geniuses. Thanks
  2. V

    Cold Rad

    You are right and thought it may be the same problem but it was open when i checked. Thanks
  3. V

    Cold Rad

    You win! Did what you said and switched off other rads. Its warm and no more grief, if you know what i mean! Thank you so much! and thanks to everyone else who pitched in with ideas.
  4. V

    Cold Rad

    The bled water is clear. The water when I opened the connection on the rad to one of the valves came out slightly black. The system is older, say 6plus years, but this rad is part of a new extension. Did not change the pump or the boiler. Last year (winter) the rad came on and worked fine. I...
  5. V

    Cold Rad

    I will do this when I get home tonight. Thanks
  6. V

    Cold Rad

    I have a rad that remains cold no matter what I do. I can open and close valves at both ends. I can bleed the rad from both valves, I mean I can close the right one and still get pressure from the left to bleed - and I can also close the left valve and bleed by opening the right one. The right...