    Ravenheat DHW Question - Newbie!

    I had the same problem with mine. First thing you should try is to change the CH thermistor. I know it sounds strange, since your problem is with the HW, but the design if the boiler means that in HW mode, both thermistors are important. The CH and HW thermistors are the same, so just put...
  2. R

    radiator output poor downstairs

    That suggests that the system is fine, and your issues are either a poorly pump, or incorrect balancing. What about if you turn down the lockshields on the hottest rads (close them fully, then open one turn) and fully open the lockshields on the coldest ones? (before you do this, please...
  3. R

    Best way to attach thermo mixer shower to combi boiler?

    That's how I did mine, and it works fine (same setup: thermostatic mixer shower off a 24 kW combi). It's much better than the nasty electric shower I had before! :)
  4. R

    ravenheat combi boiler rsf 820-20

    The CH flow pipe getting hot (when the CH is off and the HW tap is open) is incorrect, and does indicate a faulty DV. If you run the HW tap for a long time (10 mins), the rads will probably start to warm. It does seem strange, though, that you've had the same issue with your old DV. So...
  5. R

    ravenheat combi boiler rsf 820-20

    When you say that the big CH flow pipe from the boiler got hot when you used the hot tap, where were you touching it? About a foot away from the boiler? It does indeed sound like the diverter: it does two things... 1) detects the hot tap being opened 2) controls the CH water to heat the hot...
  6. R

    Ravenheat Little Star Hot/Cold Water Issue and Pump Speeds

    My RSF84 is similar. I have to leave the DHW temperature control potentiometer at approximately 1pm. Any higher, and the boiler will overheat and cut-out. There are some other posters on this forum with Ravenheat boilers and the same scenario - the consensus seems to be to leave the control...
  7. R

    Boiler schematic explanation

    I've got an earlier boiler (Ravenheat RSF84ET), which has a very similar heat exchanger design. I agree with your gas engineer. Ravenheat are correct in that the CH water should not ever mix with the tap hot water, but they are coiled together in the heat exchanger. When you switch on a...
  8. R

    Hot water starts warm then runs cold

    When you open your hot tap, does the microswitch in the boiler click, and the boiler fire-up? Does the water get hot? Does the boiler start to switch off and on, resulting in water going hot/cold/hot/cold/...?
  9. R

    CH - tapping/dripping sound

    Hi all, My combi CH/DHW has been working OK, but has recently started making strange noises. A few minutes after you turn the heating on, you can hear the sound of tapping and dripping in the pipework. It's particularly bad on the main bedroom radiator, the small bedroom radiator, and the...
  10. R

    Ravenheat RSF 84et- Hot water not not enough!!!

    If your CH is cold, and switching on a hot tap causes the CH to warm, then yes, your DV is passing. The boiler is trying to heat the HW and CH, which is doesn't have the capacity to achieve! For what it's worth, I experienced this exact situation with mine. The diaphragm failed on the DV...
  11. R

    Ravenheat RSF 100ET Boiler problems

    I had a similar problem with my Ravenheat 84 (99% the same as your 100). I replaced the entire diverter with a generic cheapo one from BES/Banico, as the HW pin was not activating reliably. The new one activated perfectly, but decided to pass to the CH when the HW was in use. I suspect...
  12. R

    Ravenheat RSF 820/20 water too hot

    I had a similar problem with a similar boiler. It turned out that the DHW thermistor was not connected to the PCB - somewhere in-between there was a break in the cable, and/or a poor connection. If you turn the DHW potentiometer (the control you referred to) up and down, you should see the...
  13. R

    Boiler Installation Certificate

    Personally, I'd forget about it. In the unlikely event that the purchaser's solicitor asks you about the boiler, simply state that you cannot remember when it was installed or last serviced. Point out that THEY are more than welcome to come round and test the hot water and heating...
  14. R

    ravenheat diverter

    I know I pointed out the BES valves earlier (due to the low price), but I've just noticed this thread: http://www.diynot.com/forums/viewtopic.php?t=82850. Perhaps they are not so good after all?! Another reference I've found is http://www.ezypart.co.uk/parts/part_id__2024 which claims to be...
  15. R

    ravenheat diverter

    BES Ltd. sell diverter valves and associated items for much less: http://www.bes.ltd.uk/products/114.asp I've not seen them for sale anywhere else at this price.
  16. R

    Combi boiler getting too hot (so then cycling)

    Hi all, I'm posting a new thread about this as I've tried quite a few things recently, and the old one was getting a touch cluttered. Anyway, I've got a Ravenheat RSF84ET combi boiler which is getting too hot and so cutting out (after 20 seconds or so, it cools, so re-fires, and the cycle...
  17. R

    Ravenheat RSF84 - DHW goes hot and cold

    Also, the manual claims there to be two fuses: two on the control PCB, and one in the gas valve PCB. After lots of searching, I started to suspect that only the SIT gas valve PCB has this fuse, and my Honeywell does not. Guess I've blown up the control PCB. :( Slugbaby: I tried to give...
  18. R

    Ravenheat RSF84 - DHW goes hot and cold

    There are two fuses on the main PCB (right-hand side) but they both check out OK. Within reason, an incorrect wiring connection really shouldn't kill anything - so say my electronic engineer colleagues.
  19. R

    Ravenheat RSF84 - DHW goes hot and cold

    DISASTER! I couldn't cope with not knowing, so I ordered a new pot set. After fitting them, the hot/cold cycling problem seemed much worse, even if I backed off the HW pot setting! I decided to put the original pots back in, and just accept that it didn't make sense. Unfortunately, I...
  20. R

    Ravenheat RSF84 - DHW goes hot and cold

    I've just tested the clip-ons with a multimeter, and I'm getting similar resistance values. And I was quite amazed how quickly it responded when moved to a chilly wondow-cill! :) The sensors in the boiler also seem to have logical readings - the wet and dry ones are the same value. Perhaps I...