  1. R

    Underfloor heating problem

    the thermometer on the flow shoe anything from 50-60 degress. when I have the mixer valve set to say 45 the temp guage on the return shows 30 ish at say 2 ltr /min. I know the difference should be about 8-10 degrees . the last plumber said he thinks by looking at the water in the flow gauges...
  2. R

    Underfloor heating problem

    yes the flow pipe to the "cold" room is very hot, the return comes back luke warm , does get a bit hotter when I turn the mixing valve up or the crank the flow right up.. screed I believe. haven't tried to touch trace the heat.i guess I can try that later. the way the floor and pipes are layed...
  3. R

    Underfloor heating problem

    What problems can the manifold have? Not actuator as I have taken them off and let the system run ..
  4. R

    Underfloor heating problem

    Hi. They have worked before. How would I know if there's a blockage? When I purged that loop the flow showed 4 ltr/m . How do I know if there is some bypass as mentioned above? Room still cold even if only one on
  5. R

    Underfloor heating problem

    Morning. Yes they have worked previously. As we're fine when my 1 kid slep there.
  6. R

    Underfloor heating problem

    all the actuators are controlling the right rooms..if that's what you mean?
  7. R

    Underfloor heating problem

    g.m sir. I have yes...I also tried to purge that loop of air and when running the water thru got 4 ltr/m flow too...? I have the mixer at 45/50 degrees... I have had the cold room running all day with the actuator removed..still nothing.
  8. R

    Underfloor heating problem

    Good morning all. I have a wet UFH system that seems to have stumped 4 plumbers etc.2 of the rooms just don't heat up at all. The other 2 zones do. Have a new pump , the last engineer said wasn't air locked..can adjust flow from 0 to 4 ltr/m but nothing seems to work. Any thoughts / suggestions...