  1. G

    RCBO tripping - identify likely location - help.......

    A short update. I deconstructed the 2 main lighting cct connection boxes in the loft, where I cut an access hole. It was like trying to arrange spaghetti with 1 hand 10inches down a rabbit hole - working in that access space... I tested all legs for N+E. And found the problem cable - it was...
  2. G

    RCBO tripping - identify likely location - help.......

    Hi, yes good spotting. I did write in the previous post with the photo the earth connections on all the junction boxes are made around the back. But there's quite a lot of text in this thread now, so I understand why you didn't see it. Bit unconventional? I suppose it was done because they're...
  3. G

    RCBO tripping - identify likely location - help.......

    When I get this basic insulation tester and need to test the lighting cct, neutral and earth, im assuming I need to remove all led bulbs in lamps and disconnect the start of led ceiling down light cable runs to exclude? Unfortunately l, the outside two lights are not the obvious fault as I...
  4. G

    RCBO tripping - identify likely location - help.......

    So, some updates. I rechecked my multi meter impedance testing of the circuit with the live and earth of the outgoing wire disconnected and I was wrong. There is no reading between Neutral and Earth with the earth wire disconnected from the earth bar of the consumer unit. I must have tested...
  5. G

    25mm core for 22mm outside frost resistant hot and cold tap...

    Ok thanks @Razor900 and @Madrab. I already had the long sds plus masonry bits so I did as before and suggested here. Pilot 10mm, then 20mm, then 28mm. Before going through the plaster inside I turned to drill only without percussion. All turned out fine. Thanks. Few photos. Now for...
  6. G

    RCBO tripping - identify likely location - help.......

    I should of just asked for it. But this fault showed itself when an electrician did a cu change out. So the quote was for all RCBOs. The lighting cuts were on the non rcd protected side of board. So he changed the cu, then said I had a fault and he couldn't use the rcbo... I know, what he...
  7. G

    RCBO tripping - identify likely location - help.......

    Yeah ok. Thanks. I'll double check what i,m telling you tomorrow. Which i guess indicated a dead short between neutral and earth ..... somewhere. The switches just have live in and out. So all neutrals in loft. There aren't many ceiling roses anymore. Maybe 2 most have been changed to...
  8. G

    RCBO tripping - identify likely location - help.......

    Ok. Board turned off at double pole isolator. Neutral removed from mcb. (Edit. Actually neutral of problem cct removed from board neutral termination.) Multimeter set to 200 ohms. Between neutral and earth of problem cct. 1.5 ohms. Between neutral of problem cct and earth connections on...
  9. G

    RCBO tripping - identify likely location - help.......

    You're right. But I will either go and buy one or I could remove one from an active cct to carry out tests. So will progress someway and report back. Thank you.
  10. G

    RCBO tripping - identify likely location - help.......

    Thanks all, just catching up. Thanks for the pointers and suggestions. I will start and turn all power off and look what my multi meter says for resistance between neutral and earth on the faulty lighting cct. If I've read the instructions right. I will re-read again before carrying out. I could...
  11. G

    25mm core for 22mm outside frost resistant hot and cold tap...

    Yeah ok. Thanks. Just quite rare and not in a brand I recognise but I may just go with it. On the cheap side. But I am only doing 2 holes!! Is that a normal arbor thread or is it for a specific core drill. I will do some searching... Tks Thanks for the other replies as well. Yes, I could use my...
  12. G

    RCBO tripping - identify likely location - help.......

    Oh, ok. I though sometimes, especially upstairs / down stairs lighting, a neutral is borrowed from within the house, from say the downstairs lighting or vice versa because it was closer / more accesible at time and does not cause an over current situation but will cause an RCBO to trip because...
  13. G

    RCBO tripping - identify likely location - help.......

    thanks, yes - I checked outside lights thoroughly including junctions in roof space. There's no sockets in this case as it is lighting only. I could disconnect dimmers, there is only 1 or two downstairs. It is not overload as the electrician mumbled neutral / earth leak. I didn't hear it but...
  14. G

    RCBO tripping - identify likely location - help.......

    yes, exactly what the original electrician mumbled..
  15. G

    RCBO tripping - identify likely location - help.......

    Started a few months ago at time of CU change out to new RCBO unit, so fault probably inherent for who knows how long....anyone's guess.. be interesting to see the IR test results for the circuit First things first - if you can take out all the bulbs on the affected circuit. Then turn the MCB...
  16. G

    RCBO tripping - identify likely location - help.......

    edit: an RCBO trips straight away, and was tried with an alternative, so it was "temporarily" replaced with an MCB to give service. Slightly longer back story that I can fill in if you want with lots more detail but I don't think will add much to the following explanation A registered...
  17. G

    25mm core for 22mm outside frost resistant hot and cold tap...

    Very straight forward question but not sure why it seems so limited or I have lost my googling abilities..... There seems to be very few 25mm cores to go through a brick and block cavity wall circa 300mm.. The supply tails on the outdside hot and cold tap, which incorporate the valves, run back...
  18. G

    RCBO tripping - identify likely location - help.......

    Hi All, Is there a effective, efficient way to go looking for a wiring fault tripping on downstairs lighting cct? Ideally, for me to go looking with a multi meter but otherwise, if I have to, an electrician with a proper testing machine..... Currently the cct is operating on an MCB. It is...