    LED lights failing

    Yep. Almost immediately on powering on.
  2. S

    LED lights failing

    Fitted Tuesday afternoon, lights have survived since then.
  3. S

    LED lights failing

    Update. After some email dialogue with the lighting manufacturer, a 5uF capacitor across the transformer secondary has fixed the issue. No buzzing or failing lights. Thanks all again.
  4. S

    LED lights failing

    Yep, although there is no neutral easily available.
  5. S

    LED lights failing

    The fittings have failed with nothing else starting or running, either on this equipment or elsewhere in the building so I think I'm ruling out voltage spikes or variations. I might look at what filtering I can fit after the transformer, and give the transformer supplier a call, might be a...
  6. S

    LED lights failing

    Could you expand on "in a way" at all, please?
  7. S

    LED lights failing

    https://www.ete.co.uk/product/transformer-380v-480v-to-110v-or-220v-50va-wide-input-voltage/ The project is modifications to an existing piece of equipment whose existing supply is TP + E..
  8. S

    LED lights failing

    Yep. Measured 230V at each light. Lights are controlled by a contactor.
  9. S

    LED lights failing

    http://redarrowtrading.com/300w-smd-ac-floodlight-photocell-6000k-black.html
  10. S

    LED lights failing

    On a project where I have got 8 off 300W LED fittings on a radial circuit from a 400 to 230V transformer. The fittings are 230V supply, and keep failing either straight away or after a short time, except the one nearest the transformer, which is fine. The fittings also seem to hum, so maybe a...
  11. S

    Consumer Unit - Advice, thoughts, suggestions sought.

    Do we try to guess what those suggestions are? RCD protection?
  12. S

    Underground electric gate motor control advice ?

    I'm guessing there are regulations for electric gates, and that you have a duty of care to people using the gates, and that lashing a panel from a roller shutter door onto the gates without the appropriate safety devices and design doesn't quite meet those requirements. I've no doubt I could...
  13. S

    Shower Pump Under Bath with an UK 3Pin Plug with FCU

    Is there not a requirement to comply with 552.1.2 in the yellow book, or does the motor have built-in overload protection? Just asking, I don't know for sure, although I would assume there is a requirement to comply.
  14. S

    Ei2110 multisensor smoke alarm

    I have Ei smoke detectors, rest assured, you would struggle to sleep through them :)
  15. S

    Most Effective Location For Smoke Alarm On a Landing

    If you're putting that amount of work in, fit a separate test and alarm silence switch.
  16. S

    Most Effective Location For Smoke Alarm On a Landing

    I would have thought they are all equally effective. You're overthinking it, it's smoke, it will drift around in the breeze...
  17. S

    Industrial round plugs (16 A/32 A)

    Also 50 or 60 Hz depending on where in Japan you are.
  18. S

    Industrial round plugs (16 A/32 A)

    Yes, 200V p-p
  19. S

    Industrial round plugs (16 A/32 A)

    Off-topic.....Currently working on a project with 3 phase + N + E blue c-form connectors.....didn't even know they existed prior to starting the project. The project is in Japan, where mains supply is 200V three phase, either 50 or 60Hz depending on location.
  20. S

    Ceiling Downlights

    I would think it cheaper to patch up the ceiling and fit a pendant than buy more downlighters. A bit of plasterboard, timber, filler and white emulsion.....job done. Probably some MF boxes too.