  1. B

    Cables in conduit

    I could put it there and use crimps for connections but the floor above is going to be a tongue and groove oak floor so it will be very hard to get to the connections once the floor is down, and so does this not present another problem? Is there any other way you can think off running it down...
  2. B

    Cables in conduit

    I'll have to take some photos next week now sorry mate as i have left the job, thanks for the suggestion of an adaptable box but that will prob look a bit ugly stuck to the ceiling.
  3. B

    Cables in conduit

    I thought it only gave you the figures for single cables in the on site guide Anyway i thought it would be to many cables anyone got any ideas on how else i can do it then to stay within the regs but also keep it looking ok and within character of the stone wall.
  4. B

    Cables in conduit

    I've recently been asked to second fix a house that was already first fixed. The switch by the door is a 6 gang switch and on a stone wall, so the owners have asked for the cables to be run in conduit down the wall. Is it possible then to put 3 x 1.5mm twin and earth cables and a 1.0 mm 3 core...
  5. B

    Circuits tripping after consumer unit change.

    I've recently changed a consumer unit at a persons house and when i turned it on it began tripping the rcd. So now i've taken out the main rcd and moved them onto rcbo's and told the owner that i will sort out the circuits that are tripping. Now i know that with the current regs everything must...
  6. B

    Zs value and loose connection

    Seemed to have sorted it now when i got back to the job i decided to run another zs test on the shower only this time it gave me 3.??, so then i went round and checked every connection which were also tight. Then after a bit of head scratching i decided to change the rcbo for an mcb and got i...
  7. B

    Zs value and loose connection

    Only about 20 m long and yeah it was calibrated about 2 months ago, would old batteries be giving readings like that?
  8. B

    Zs value and loose connection

    Its a 10mm2 cable for a shower and i took one reading and it said 1.79 then another and it gave me 0.64.
  9. B

    Zs value and loose connection

    If you have a zs value that is within the allowed regulation is it still possible to have a loose connection? Sorry about some starting so many threads. I just worry loads. :(
  10. B

    High zs on shwoer circuit

    10.0mm and about 20 metres. Isn't 0.64 with in regs though?
  11. B

    Running swa in same trench as oil line.

    First of all i've already posted 2 new threads on this forum and have had a good informative response on both so thank you all who posted, really nice to no there are people out there so willing to help others. Second thing and my main point i've been asked by a builder to run an swa to a...
  12. B

    High zs on shwoer circuit

    Its all sorted now i went and took another reading and it was 0.64 with a ze of 0.24. Don't no why it was so high last time though?
  13. B

    High zs on shwoer circuit

    I've recently installed a shower circuit for someone but when i come to test i can't seem to get the zs value for my showere below 1.79, which i no is high, the shower is on an rcbo i just need to no what i can do to get the value down and why this could be happening.
  14. B

    Neutral to Earth fault through Edison screw lamp?

    But i'm not testing between switch live and earth it is between the neutral and earth that there is a problem. Also when the power is turned on the light is coming on.
  15. B

    Neutral to Earth fault through Edison screw lamp?

    Iv'e recently been doing the electrics for a new bathroam have made sure everything is on rcbo's. The main problem i have is that the old electrics are in a very bad condition and the lighting circuit for the bathroom area was showing up a neutral to earth fault so after looking in the attic for...