  1. C

    Apha combination boiler problem

    Without model details I can't advise much. I do know the Alphas have a stupid flow switch on the water main inlet. I don't work on them much but has your plumber checked this? If you provide model details you'd get more help.
  2. C

    Potterton Netaheat - one for the GasSafes

    Parts are most available. I would strongly suggest considering replacement. If these boilers go wrong, they do so spectacularly with bad results. The casings on these (most of the range) are positive pressure. That means if there was corrosion or damage, the case can spew out products of...
  3. C

    Hot water size

    A lot of combis out there will have a 15mm inlet on the cold water inlet. Its not as simple as "it's a 15mm connection so 15mm will do". Each system needs to be carefully considered as you may have low flow rates, poor pressure etc. In cases where there are issues, you may see 22mm (rarely...
  4. C

    re;honeywell wireless thermostat

    It would depend how you have this wired. I'm assuming you have a multimeter or means to test this... On the stat terminal base there are two terminals marked A & B. If you have 230v on terminal A then you have a supply to the stat (be it from the boiler or spur) then the stat would...
  5. C

    Water storage tank leaking!!

    It does sound like a Fortic tank. The fact it's got a storage vessel on the top, would strongly suggest its vented. Your local plumbing merchant would be able to obtain one for you but I would be surprised if they had one in stock. Here's a link for you...
  6. C

    Descaling hot water cylinder?

    Sentinel x800 is good too (jet flo). Can be used for power flushing or residual circulation. I've found this to be good for both Carl
  7. C

    fitting new syncro switch on honeywell 2 port valve

    If you weren't supplied with the plastic cap type crimps you can use normal crimps.
  8. C

    fitting new syncro switch on honeywell 2 port valve

    Hi, Doesn't matter which wire to which wire! Just cut them and join them. The plastic caps are crimps.cjust pop the wires into the cap and crimp shut, preferably with a crimp tool. Good luck Carl
  9. C

    water pipe repairs

    Water mains often form a earth bond from your house electrics, as does your gas main. I've heard story's of people getting belted when they haven't cross bonded a gas pipe when cutting it out. I think it is incredibly rare. In the gas game, we use what are essentially car jump leads. The...
  10. C

    Recharge air in expansion vessel.

    I use a regin hand pump myself. I threw away the valve (agree its total crap!)and replaced with one of a cheap halfords foot pump. Never had a problem since!
  11. C

    noisey when hot water comes out of taps

    Have you modified anything near the cylinder? I'm assuming you have an indirect vented cylinder? The Hot water pipe leaving the top of your cylinder (the one bang in the middle, right at the top) should be angled slightly upwards towards the vent. The vent goes up to the cold tank and hangs...
  12. C

    Problems with my shower - any help much appreciated!

    Hi, First off id be checking the strainers in the hot and cold supplies to the shower. There is usually a mesh strainer on each supply. I've also had a customer complain of this recently and found her shower head so badly scaled up, nothing could escape it! Check this also and if required...
  13. C

    Worcester 24CDi Ignition Lockout

    Sorry to sound like a nag but this one needs looking at by an engineer! It will require removal of a part or two for investigation and this will require case removal... Sorry!
  14. C

    Worcester Greenstar 37CDi - Luke Warm Water Only -heating ok

    You may be getting a bit of cross flow. It is possible the mains was pushing through the bidet tap and pushing mains water into the hot system, therefore, cooling it down. A long shot but dificult to say without having a look. Perhaps the non return valve is knackered in this tap or not...
  15. C

    Suitable shower

    Have a look at this... http://www.aqualisa.co.uk/upload/INSTALLATION%20GUIDES/Install_QtzDigExp_adj.pdf It gives the processor dimensions and probably the rating of the supply. I think it's 3 or 5 amp. Im sure there is no issue with a direct cylinder. I've just realised you put...
  16. C

    Worcester Greenstar 37CDi - Luke Warm Water Only -heating ok

    To be honest I don't know as I've never asked them to come out. Give them a call on 0800 408 5500.
  17. C

    Suitable shower

    Just make sure it's the pumped version. It might be prefixed on the model as HP. Ask the merchant anyway.
  18. C

    Suitable shower

    http://www.google.co.uk/products/catalog?q=aqualisa+quartz+pumped&oe=UTF-8&hl=en-gb&client=safari&um=1&ie=UTF-8&tbm=shop&cid=9159958560624483546&sa=X&ei=EPIGT5agDdKDhQft5tC7CQ&ved=0CEsQ8wIwAg
  19. C

    Suitable shower

    A quartz would work! As long as the processor is lower than the tank you're ok. This is usually easily achieved as the tank is on a stand in most cases. The hot water is not a problem. If the processor can't be put in the loft, an airing cupboard will do. The quartz is an all in one...
  20. C

    Worcester Greenstar 37CDi - Luke Warm Water Only -heating ok

    No problem... I am very concerned you said you've moved your flue up as it was dripping. It sounds like the flue hasn't been sealed up outside and your gas engineer should never do a temporary job on a flue!! If Gas safe knew you were left with an unfinished flue or flue left in a dangerous...