  1. A

    Valliant AquaPlus VUI 362-7 Help!

    Knocked d0 down to 15 and no difference, boiler fires up stays on for a few mins then goes into overrun. Wondering whether it’s pump related or poss diverter valve?
  2. A

    Valliant AquaPlus VUI 362-7 Help!

    Can anyone help with this maybe I’ll need to raise another thread?!?!?
  3. A

    Valliant AquaPlus VUI 362-7 Help!

    Bump any help guys? @Agile @The831Bunny @ianmcd
  4. A

    Valliant AquaPlus VUI 362-7 Help!

    Just got home and checked d0 settings, it’s at 30....should it be at max?
  5. A

    Valliant AquaPlus VUI 362-7 Help!

    https://www.diynot.com/diy/threads/vaillant-ecotec-plus-630-error-s7.352248/ Issues seem similar to above link from searching, but can't from that pinpoint where to start. Do I need to start looking at d0 etc? Maybe a pump clean? the PRVs were proper crudded up...hence replacements were required.
  6. A

    Valliant AquaPlus VUI 362-7 Help!

    Hi @ianmcd @Agile @Dan Robinson So the 10bar blue PRV was the culprit in the water overflow outside, it’s been replaced and all good. boiler is all back and running with no leak or overflow. Only thing is now I’m getting odd behaviour and what seems to be a repeating pattern ending with an...
  7. A

    Valliant AquaPlus VUI 362-7 Help!

    Had the boiler on yesterday and came home to find the blue 10bar PRV dripping constantly, luckily had a bucket below but it dropped 10litres if water over the whole day. ordered a new one and also heatx
  8. A

    Valliant AquaPlus VUI 362-7 Help!

    Last question hopefully until the plate arrives. Filling loop... should I be opening the front most one (inlet) to max, then open rear one until pressure up to 1.5bar. Then close rear and front? Just want to check I don’t need to leave one open? also, getting a pump overrun status code, is...
  9. A

    Valliant AquaPlus VUI 362-7 Help!

    ahhh and that’s causing the leak? on the airlock question do I just need to make sure the pump aav is loosened a little to allow system air to escape properly? I’ve bled all the rads ready
  10. A

    Valliant AquaPlus VUI 362-7 Help!

    Thanks @ianmcd - would that be causing the dribble? So definitely no more valves or anything like the 10bar dhw valve? the PRV was pretty cruded up so glad I replaced. will get the heatx off and see if it can be cleaned or flushed if not will go new. the airlock - how should I clear that...
  11. A

    Valliant AquaPlus VUI 362-7 Help!

    Sorry for all the questions at once! strangely with the boiler off and the cold mains valve shut I still get some water coming when hot tap is on, but I can only assume that’s due to mixer taps, rather than something passing... appreciate all your help @ianmcd, hopefully I’m almost there to...
  12. A

    Valliant AquaPlus VUI 362-7 Help!

    Hi @ianmcd PRV arrived today and just fitted it. The vent pipe outside is still dribbling water when I’ve set everything. steps I followed : released system pressure, replaced PRV, leaving drain valve open repressurised the EV to 0.9bar. Closed drain valve. opened cold inlet main feed. Opened...
  13. A

    Valliant AquaPlus VUI 362-7 Help!

    Thanks @ianmcd with the pressure rising overnight after charging the EV, is that down to the PRV again or is there something else I need to be considering? Cold water pressure here is quite high so maybe I need to down mains pressure down?
  14. A

    Valliant AquaPlus VUI 362-7 Help!

    think I have the PRV today? Should I drain like you showed me other night? also my boiler has a small 1litre expansion vessel underneath the main one - does this need pressurising as well?
  15. A

    Valliant AquaPlus VUI 362-7 Help!

    Morning @ianmcd left boiler with cold feed on overnight and the pressure on the control unit gauge has risen out of the “green”. Is this all attributed to the PRV still or should I be looking at another valve to change same time as the PRV? PRV is on order
  16. A

    Valliant AquaPlus VUI 362-7 Help!

    So the blue dhw wouldn’t be passing also? I’ll order and replace the grey
  17. A

    Valliant AquaPlus VUI 362-7 Help!

    now I’m confused there are two PRV. One ch and one dhw. Which one do I need based on fact it overflowing and there’s no ch demand switched on?! assume dhw is blue cap, ch grey cap
  18. A

    Valliant AquaPlus VUI 362-7 Help!

    is the procedure similar to drain the boiler like I did for the PV and then just replace the unit? Assume it’s just this I need?
  19. A

    Valliant AquaPlus VUI 362-7 Help!

    Awesome thanks I’ll sort a new one and replace it if that’ll be the culprit for the leaking overflow
  20. A

    Valliant AquaPlus VUI 362-7 Help!

    Thanks Ian. So I’ve drained the expansion vessel, must have been 8litres in there, repressurised to 1bar and filled the cold loop to 1.5bar on the control unit gauge. Boiler back on and ran the hot tap. Pressure looks stable so far holding in the green at 1.5bar. overflow pipe outside is still...