    Baxi megeaflow 28 he

    Demo model? How was it run? Is the injector/restrictor correct size(is it setup to work on LPG whereas you're using it on NG)
  2. P

    No Hot water but Central heating works ok

    First port of call would be flow switch. Since the boiler doesn't seem to be recognising a demand for water If the boiler were firing then there could possibly be an issue with other components.
  3. P

    Boiler not firing, no H/W or C/H

    Re my earlier post. orange and white wires are found on the mid-pos valve mid position valve wiring. CH turned on White wire to earth/neutral (230v) indicates heating demand to valve Orange wire to earth/neutral (230v) indicates power to pump/boiler
  4. P

    15YO boiler condemned as flue too long??? Please advise?

    Silicon is not a suitable material to hold a flue outlet together. nor is a flue terminal held together by concrete
  5. P

    Boiler not firing, no H/W or C/H

    230v across both what?? the stat or the on at the boiler?
  6. P

    fault code on boiler?

    Gas valve or electrodes GSR engineer
  7. P

    15YO boiler condemned as flue too long??? Please advise?

    Reattached :? I'd say that needs looking at.
  8. P

    WARNING VAILLANT 837 commbi boiler

    Valliant built there name and reputation on producing sub-standard boilers at a high price and ignoring customers :? I doubt this entirely. Maybe a bored sparky at work :lol:
  9. P

    Boiler not firing, no H/W or C/H

    Also when you test live-neutral you should also test live-earth and neutral-earth this will help eliminate problems with faulty neutrals
  10. P

    Boiler not firing, no H/W or C/H

    Test the boiler/pump live. If you have a mid position valve as you say this is the orange wire. Turn your heating on you should have 240v on the white wire to the valve and also 240v on the orange wire. If you are not getting 240v on orange suspect an issue with the midposition valve
  11. P

    Pressure valve??

    What is the pressure at on the boiler? Cold it should be 1 - 1.5 bar when the system is hot is should be 2 bar or so. If the pressure is continually high i.e 3 bar when hot or cold then you have a passing issue either via the filling loop or another part where the water and heating pass...
  12. P

    Boiler not firing, no H/W or C/H

    Does the pump run?
  13. P

    Worcester 30si Boiler Pressure Gauge

    1-1.5 bar when cold. You need to unscrew the front panel and fold it down. Then the pressure gauge will push in from the back. It's on 2 little clips
  14. P

    Expansion vessel change.....

    Highflow 400 plate heat ex they were fun Most things Worcestor were not easy to change. I used to have fun swapping the big cast heatslave water tanks
  15. P

    Expansion vessel change.....

    No they are behind the pump and DHW heat ex and you have to strip a lot out to get to them.
  16. P

    Baxi Combi Instant 80 HE Preheat function

    Leaving the preheat function on uses more energy both gas and electric as the boiler fires in order to maintain it's heat. If you have short runs of pipe then it really isn't required however with long runs you may be drawing off more water in order to get the boiler up to temperature. If you...
  17. P

    Boiler bar to high

    Is the PRV dripping outside (boiler overflow) sounds like with that pressure increase when heating up there is an issue with the vessel
  18. P

    Biasi combi knocking noise.

    I presumed you said the knocking was coming from the boiler when you said top condensor tank area (on the m96 this is the recouperator) If it's coming from the pipework and radiators it's likely expansion on the pipework when the system first heats up where a pipe is fitted close to say a...
  19. P

    Strange Dripping Overflow

    If the pump is running and the open vent is discharging into the F+E then as stated above the system is pumping over. This could possibly be a result of insufficient head on the pump/pump speed too high or restriction around the cold feed/open vent area or even down to how the system is...