Search results

  1. M

    Seeking advice on supplying two outbuildings

    Hugely helpful John, thanks very much for taking the time. I'll take this all on board and have a chat with an electrician and see what, if any, they're happy for me to do myself. Thanks again!
  2. M

    Seeking advice on supplying two outbuildings

    Thanks for the replies, most helpful. Assuming I did want to go down the local TT route for the outbuildings, can anyone clarify the below points for me? I'm not 100% I've got it right in my own head. Thanks!
  3. M

    Seeking advice on supplying two outbuildings

    Thanks for the reply. Sorry, of course the lighting would be radial my mistake. It was my understanding that PME earth is not supposed to be exported outwith the "equipotential zone, i.e my house? It's often done but not supposed to be done? I thought the requirement for metal CU's was for a...
  4. M

    Seeking advice on supplying two outbuildings

    Hi all, I'm after some advice and clarification on a few points for a proposed supply to two outbuildings in my garden, a shed/workshop I've just built and a small BBQ cabin further down the garden, neither of these have any water/gas supplies into them and are of timber construction. Firstly...
  5. M

    Supply type identification and opinion on earth loop reading

    Thanks for that I'll get straight on to them. A little more information has come in from the previous owner via email, the floors are solid concrete but apparently the "main supply does come in there" and it's definitely the documents they got for those jobs, their name and address is on one of...
  6. M

    Supply type identification and opinion on earth loop reading

    Ok so thanks for all the replies. So what should I do? Contact the supplier SP Energy Networks and have them assess it?
  7. M

    Supply type identification and opinion on earth loop reading

    Ok, so a little update. I've spoken to the previous owner and they've forwarded me the two certificates of installation and it seems that actually the supply is TN-C-S, confirmed on both. The house was fully re-wired in 2012 and this electrician tested it all and fitted a new CU, here is the...
  8. M

    Supply type identification and opinion on earth loop reading

    Can't take credit for that one, we only moved in a year or so ago and it was already like that. So.... here's some pics of the CU open, and one pic of one of the "mains" tails next to a core from a 10mm 3-core SWA (for size, looks like 16mm to me?). Cheers
  9. M

    Supply type identification and opinion on earth loop reading

    It's this one Wylex NHRS6606, metal for sure. http://4841-nhrs6606.aboutsemi.com/
  10. M

    Supply type identification and opinion on earth loop reading

    Thanks for this. Replies above. P.S, we're only assuming this is a TT supply based on what we can see, it may not be the case but the loop reading would seem to indicate it he says.
  11. M

    Supply type identification and opinion on earth loop reading

    Thanks for the reply. Now that I don't know, it may well be >200 ohms, perhaps the MFT displays that as an upper limit, I didn't ask? I have no way to know where the electrode is, it's a 1950's end terrace ex council, certainly no sign of one outside that I can see (and I've had a good look)...
  12. M

    Supply type identification and opinion on earth loop reading

    Hi all, Thanks for taking the time. I'm looking to supply power to a shed/workshop I've just built a few metres from the house, and from there down a 25m run to a small BBQ cabin. So I've had an electrician out to quote for the job this morning left concerned that the supply was not earthed...
  13. 23468311_10155671026450575_529454339_o

    23468311_10155671026450575_529454339_o

  14. Elecs

    Elecs

    Electrical photos from my home
  15. M

    Timber frame window and door openings, waterproofing advice...

    Cheers for the replies gent's, much appreciated, not too worried about the cost as it's only two small windows and a door opening, just want to do it right. Cheers!
  16. M

    Timber frame window and door openings, waterproofing advice...

    Hello, I'm building a decent size timber workshop/shed at home. I'm effectively building it like a common US timber frame house, lined inside, 4x2 framework, insulated, breather membrane then cladding the outside with T&G tanalised shiplap cladding. The windows and door are double glazed...
  17. M

    Shed base / floor - insulation and damp proofing?

    58 views, no opinions? Would really appreciate any advice! ;)
  18. M

    Shed base / floor - insulation and damp proofing?

    Hello, I'm building a 9ft x 14ft shed/workshop and i'm after a little advice as it's the first time I've done anything like this. I've excavated and prepared a base consisting of, weed control/driveway membrane, 5 inches of compacted type 1 then a screeded 50mm sharp sand/cement 6/1 dry mortar...
  19. M

    URGENT - Dimmer switch wiring help!

    pjcomp & TicklyT thanks for the helpful replies, much apprecited. I actually followed the dodgy diagram that came with the dimmer but I'll put my hands up and say that I clearly am a complete novice.. I did manage to change all the double sockets, cooker switch, immersion timer override...
  20. M

    URGENT - Dimmer switch wiring help!

    Hi all, sorry about the urgency here but im currently in darkness in my kitchen. I've just fitted 2 x dimmable spot bar (4 x halogen bulbs on each) lights in my kitchen. There's just one switch, it worked fine with the old switch. When I removed the switch the only points on the back is...