  1. C

    Electrical Installation Installation and Testing

    Yes I am planning to enter the SUM of the measured Ze plus the measured R1+R2 - This would be a calculation, being the sum of two measurements (as opposed to going to a socket and doing a Zs test, which would be a measurement I was simply answering the OP who was asking why they'd raise an...
  2. C

    Electrical Installation Installation and Testing

    Cos my Zs is higher than the the calculated (which must be due to the "no trip" function being untrustworthy I believe).
  3. C

    Water tank overflow into soil stack

    OK - Do I take it I can use a Tundish/Hepvo with iunsect screen and that it will comply?
  4. C

    Electrical Installation Installation and Testing

    Think it may be different for different BC, cos when he did the first fix visit, we talked about the tests I would be doing, and he said once I'm done he'd put his tester on some of the circuits to check the work. I got the impression he would simply be checking rather than compeltiong all of...
  5. C

    Electrical Installation Installation and Testing

    hmm - what does that involve?
  6. C

    Electrical Installation Installation and Testing

    Thanks Gary - yes done the 1/2, 1 and 5 at 0 and 180 and they all look fine, but haven't done it at the board, so will do that too and take the highest.
  7. C

    Electrical Installation Installation and Testing

    :D and that's exactly why I want to calculate the Zs rather than put the result of the no-trip - the measured Zs is still more than acceptable (0.67) but is still higher than Ze +(R1+R2). :roll: If I put in the measured results BC would raise an eyebow wouldn't they?
  8. C

    Electrical Installation Installation and Testing

    OK - thank you. 1. OK - I think I was using the wrong teminology for R1+R2 - so I think I understand what you mean - r1+r2 is the figure of eight tests for the ring which will be 4 x the R1+R2 readings which should be inserted on the form. 2. Yes BC were informed, they've had their money...
  9. C

    Water tank overflow into soil stack

    Water tank in roof, but no escape for mains in if the ballcock fails. Simplest thing for me would be a device that would take the potential overflow from the tank and overflow it into the soil stack - obviously it would need to prevent smells coming back. I can't imagine something hasn't...
  10. C

    Electrical Installation Installation and Testing

    I am going through the process of ripping out some old, extending, and installing new circuits in a flat. Building control were informed and have accepted my competance, subject to payment and them checking my work etc. I am coming towards the end of my testing and wanted to ask a couple...