Search results

  1. C

    High resistance on ring circuit

    Found it with a bit of luck and a loan of a voltage finder. Traced the cable up the wall til it took a weird route off course, followed it back from the other socket. Found jb buired half way up the wall
  2. C

    High resistance on ring circuit

    Managed to talk the customer into digging a trench for the cable as he seen his neighbours overhead cable and it was an eyesore. Thanks for bringing it back up for discussion tho. Jobs a good'un.
  3. C

    High resistance on ring circuit

    I should have gone into more depth on my post. I dont own a wander lead so done it the long way by taking every socket off and testing between L-N and CPC-N i found the problem cable. It must be a joint box some where at fault. I was looking for any tips on trying to locate a joint box buried...
  4. C

    High resistance on ring circuit

    I was to asked to add a spur on a ring circuit. I done a continuity test to make sure i had a ring the N-N was 0.46 CPC-CPC was 1.08 But my L-L was 2.4, i went round every socket looking for a loose conection Tightenes up a few sockets and the reading came down to 1.9 i coudlnt find any junction...
  5. C

    Quotes for electrical work

    Had this before from someone that had an 'engineer' from currys out. It needed a cooker outlet (elephants nose) the guy called it a spur box.
  6. C

    Overhead garage supply

    I wasnt aware of that, i'll let him know thanks for that!
  7. C

    Overhead garage supply

    I had discussed this with my mate but he is happy with that as unfortunatly he wants to keep costs down, plus it will be his main fridge freezer for his house as he has no space in his small kitchen for a big fridge freezer so it might actually be best so if it trips he will know about it and it...
  8. C

    Overhead garage supply

    The lowest point of the cable will still be above the bushes. I wasnt meaning to sound so lackadaisical about the mcb i was mainly thinking that a 32a mcd which is rcd protected will be ok to protect a 6mm SWA to supply splitter with 16a and a 6a mcb's. As i said this is my first time doing...
  9. C

    Overhead garage supply

    Could anyone tell me how i am i best supporting the cable to the wire? Would ordinary cable ties be ok?
  10. C

    Overhead garage supply

    Mainly because theres a spare 32a in the DB
  11. C

    Overhead garage supply

    Sorry dont understand. What do you mean use the SWA as a fly over?
  12. C

    Overhead garage supply

    No vehicles will pass under. Thanks everyone
  13. C

    Overhead garage supply

    Hi everyone new to the site. I have been asked to wire a supply to a mates garage and i am just looking for a couple of pointers. I havent done this type of instal before so excuse my ignorace if i have a couple of things wrong. I plan on wiring overhead on a caternery wire as underground...