  1. N

    consumer unit

    Hi guys is it ok to have a consumer unit in a room with a sink and a toilet this is a rewire or will the consumer unit have to be moved
  2. N

    diversity 66% of current demand for lighting

    so then apply the 66% rule to a circuit that would supply power to kitchen,hallway,lounge and living room
  3. N

    diversity 66% of current demand for lighting

    hi guys got my self confused with diversity using conservatory as on example 6amp mcb ok lighting 66% of total current demand. I have two lights in my conservatory 100 watts each 200watts total = 0.83 amps so 66% of that is = 0.54 amps is this right or is it 66% of the 6 amp breaker...
  4. N

    Design current ring main

    Thanks for all your help gentlemen :D But one more thing after calculating volt drop and insulation. light circuit is no good.Would you split in to two separate circuits or up grade cable
  5. N

    Design current ring main

    yes sorry the breaker needs to trip before the cable set on fire
  6. N

    Design current ring main

    mmmmm so if all the appliance are on using 24 amps would it not trip a 20 amp breaker
  7. N

    Design current ring main

    so lates say washer,dryer,iron and boiler are on in utility room from looking at my appliances i get 24 amp so putting a kettle on in kitchen as well would make 33 amp not good so put utility room on a radial 2.5 t/e rated at 27 amp 32amp breaker cable approx 10m
  8. N

    Design current ring main

    15 double sockets on 70 meters of 2.5mm t/e is what i am try work out on a kitchen and utility room
  9. N

    Design current ring main

    Hi Gentlemen right if a lighting circuit has 10 lights 100watt each = 1000watt divided by 240 volts = 4.2 amps rounded up, so a 6 amp mcb to be used i believe this to be correct so if i got 15 double sockets on 70 meters of 2.5mm t/e how do i work out the design current. thank you
  10. N

    bathroom extractor

    Does the 1200mm switch height not apply in this case?
  11. N

    bathroom extractor

    Hi Gentlemen If i fit a bathroom extractor to my lighting circuit off my pull cord. does it need to be fitted to an other form of isolation switch if so were,in the bathroom or out side the bathroom
  12. N

    good or bad practice in reg or not

    was trying to stay in the safe zone as much as possible. planning officer is bit of stickler. so if going round the bottom is ok with regs thats what i shall do. will let you know what the stickler said at a later date THANKS FOR ALL YOUR HELP
  13. N

    good or bad practice in reg or not

    hi thanks for the quick reply. so you mean like this
  14. N

    good or bad practice in reg or not

    morning gentlemen please could you tell me if the wiring in picture is in regs or should i go back to the top in the safe zone. plus i am concerned with the amount space left on the right of the window ( 5" ) All is to be dot and dab cheers Gents
  15. N

    double sockets

    Hi to you all could some one please tell me how close i can but two double sockets. And how far away a switch should be from a door frame cheers