  1. Madrab

    Radiator Sludge

    I see 2 different distinction with balancing when it comes to central heating systems - 1- Balancing rads to obtain the correct ΔT across the rad to ensure the radiator is delivering its documented output and can replace the heat loss for the space it's been sized for. Also to try and ensure...
  2. Madrab

    Basin Waste to P Trap

    Does the spigot part of the flange actually fitting inside the throat of the waste? I have seen this with some 'universal' waste's before whereby McAlpine traps with that spigot type flange doesn't fit inside the waste, therefore the trap can't tighten up. I've had to trim the plastic to get it...
  3. Madrab

    Lagging for an external condensate pipe

    Ok - strictly speaking during a runaway fault condition where the other safety devices failed then yes that could happen. Not sure I've ever come across that scenario though TBF.
  4. Madrab

    Lagging for an external condensate pipe

    The only reason the Pressure Relief Valve (PRV) should lift, if working properly, is when the boiler pressure rises to >2.5bar, at that point the PRV valve will start to lift to release the excess pressure. The only reason that a sealed systems pressure would normally rise to that level is when...
  5. Madrab

    Lagging for an external condensate pipe

    Watch the system pressure when the boiler is running, does it climb up over 2.5bar?
  6. Madrab

    Hep20 or something else?

    Yup, that's exactly why and even then that may not have been enough if it was an ascending type spray bidet. Cat5 backflow protection needs a cistern with an air gap and a weir overflow, which a standard cold water cistern wouldn't have had.
  7. Madrab

    Soldering copper next to a fitting

    If it's only 120mm away then it's touch and go. The rag would need to be soaking wet and that may protect the plastic but in turn it may stop the fitting from getting hot enough for the solder to take properly. I'd remove the whole thing before soldering if possible.
  8. Madrab

    Minium room temperature, is there a limit?

    With regards to what? Temps are usually taken at height so any temp measured below 5degC can start to drop into the frost zone @ ground level, if it's like that for an extended period of time. Hence the reason for frost stats/boiler stats/TRV's etc are usually set to enable if the temp drops...
  9. Madrab

    Hep20 or something else?

    As suggested, it is against UK regulations to supply an ablution device (bum gun) from the cold mains supply in the UK. This is due to the risk of contamination of the/your mains drinking water by bacteria that will undoubtedly contaminate the end of the gun, simply by using it. Please don't...
  10. Madrab

    Shower trap strange goings-on

    Is the shower on the same waste run as another fixture that is used regularly? if so, there could be back pressure that is blowing the seal out of the trap. What is the depth of seal in the trap for the linear drain?
  11. Madrab

    110mm stack rubber seal

    As suggested, these seals usually change with age and become hard/brittle or shrink and once undone, experience has shown that they rarely seem to seal properly again. To what degree they have degraded though would be down to feel. In other words, with a little silicone grease applied, how...
  12. Madrab

    Radiator Sludge

    Bit surprised though, given the fact that sorting out and system sludge/restrictions would have nothing to do with Gas Safe or anyone else TBH. There should be confidence in the sludge diagnosis from the independent and TBH it should be relatively easy to sort out even with a mains flush, even...
  13. Madrab

    Can my valiant ecotec run just a single radiator?

    Any boiler can run just one rad but yes it will lead to short cycling and be highly inefficient.
  14. Madrab

    Converting push fit to glued?

    Yes - both pushfit and SW plastic waste pipe can be used with universal compression waste fittings. Glu'able pipe, i.e. solvent weld is 43mm OD not 40mm as is pushfit but both are generally known as 40mm or 1.5"
  15. Madrab

    Converting push fit to glued?

    For me it's a few things. Most of which I have experienced. Solvent weld is a bit like soldering copper, once it's glued properly then it can be considered part of the pipe and from a secure and low leak risk point of view, there isn't a better approach. Therefore there should be no need for a...
  16. Madrab

    Converting push fit to glued?

    Unfortunately, I think the problem here is that they could be bathroom fitters? Whilst not all are the same and your chaps may be good workers, I find that a lot of them are a jack of all and unfortunately a master of none and I find myself repairing a lot of their work when it ultimately fails...
  17. Madrab

    Fall on horizontal shower waste to boss strap

    If you can avoid it, try not using the rubber adapters. Over the longer term they can become troublesome as they age harden. If at all possible I would recommend that you either use the correct pushfit or ideally a solvent weld adapter.
  18. Madrab

    Merry Christmas!

    All the best to you too @dilalio and all the other regs as well, hope you and yours all had a great day!
  19. Madrab

    Lagging for an external condensate pipe

    Yes and if it's fitted properly, without cutting it down its length and with a good couple of coats of good quality exterior paint, that will then make it waterproof and UV resistant, seen bitumen paint used before now too. As the old saying goes though, do it properly and do it once. As...
  20. Madrab

    Lagging for an external condensate pipe

    Some boilers have trickle overflow condensate traps, some have syphon traps, the former allows a constant discharge, the latter discharges once the trap fills up enough, both types are still commonly used, boiler MANU dependent. During extended periods of sub zero temps and typically If a...