  1. A

    Gloworm compact 80e

    Hi micky, I am going to check the filter. Just thought someone may have some other thoughts while boiler drained down. Any probs encountered with boiler shut off valves or pump pipes etc in anyones experience or all generally not a problem? Regards :lol:
  2. A

    Gloworm compact 80e

    Hey thats good help!
  3. A

    Gloworm compact 80e

    :roll:
  4. A

    Gloworm compact 80e

    :o any more thoughts? regards
  5. A

    Gloworm compact 80e

    Gas.correct about the filter only in c/h and have no bearing on Dhw except that without the pressure dif switch kicking in then it cuts out the dhw as well. So indirectly does have a bearing on dhw as it wobt operate without pdv passing test first on all Gloworm compact 75/80/100`s
  6. A

    Gloworm compact 80e

    Cheers gas, Auto air vent works fine ...Pump works fine for normal usage. Heating dwh fine .As said prev..if overide switch pdv switch everyting is tickety boo. It is the pdvalve spindle that is not operating due to no pressure to the housing ( I guess)
  7. A

    Gloworm compact 80e

    :cry:
  8. A

    Replace PRV...

    :P
  9. A

    Replace PRV...

    neds, take no notice mate, you`ll find there are a lot of many good people who will give you the benefit of their experience. And some who just like preaching :o regards
  10. A

    Gloworm compact 80e

    Hi all, Could do with some input/suggestions which would be appreciated. Compact 80e is getting flame lockout intermittently, often now needs about 3 resets for either C/h or Dhw irrespective. I know pressure differential switch plunger is not pushing out to make microswitch. P/d/switch can...