Search results

  1. R

    DIY a new ring main

    I spend a lot of time in a country where 13 A radials are the norm. The only time I‘ve ever seen one of then overloaded was with multiple electric heaters plugged into one circuit. Had it been one circuit per room everything would have been fine but this circuit supplied two bedrooms...
  2. R

    help with the existing wiring of a 2 bed house

    1) You mean all sockets have two T&E cables and those two only have one each? That would likely suggest that they‘re unfused spurs and there’s junction boxes under the floor. They should be replaced with maintenance-free junction boxes. 2) This could probably be rectified by running 6 mm2 from...
  3. R

    Unusual ceiling light wiring

    Does the current light work? How many lights are there in the room? I can see two likely scenarios. Either someone connected the light wrong or the wires in the ceiling are connected the wrong way round somewhere. Use the multimeter on Volts AC and measure from red and black to earth while the...
  4. R

    Manufacturer says 15A fuse needed for 2.79kW oven

    The fusing current of a BS1362 fuse is 1.9*In, i.e. 38 A for the 20 A one. The fusing current of a B-curve MCB is 1.45*In or 46.4 A for a B32. So in case of an overload it’s likely that the fuse blows first - provided this plug is the only load on the circuit. In case of a short, the MCB is most...
  5. R

    DIY a new ring main

    Yes, two radials would certainly be an option, although in all likelyhood oversized for the expected demand. They‘d probably use less cable than a ring.
  6. R

    Is this a spur?

    So what size MCB is this fed from? If smaller than 32 A you’re good to go, if not, you need to convert this to a fused spur. I think you could even have the FCU at the end of the feed, i.e. where the socket is now. Move the socket to the right, fit a single back box with an FCU where the feed...
  7. R

    DIY a new ring main

    The beauty of a radial is that you don’t have to jump from socket to socket but can branch out in multiple directions, even from the CU. In this case I‘d probably run one cable for the hall sockets and another to the lounge. That means the lengths don‘t simply add up, it’s the length of the...
  8. R

    Is this a spur?

    Since there‘s two loads it would either have to be a radial circuit (16 or 20 A MCB in the consumer unit) or wired from a fused connection unit. You can’t have more than one double socket on an unfused 2.5 mm2 spur from a ring.
  9. R

    Manufacturer says 15A fuse needed for 2.79kW oven

    There’s no 13 A plug fuses on the continent but 13 A MCBs. No 15 A fuses either, the standard changed to 16 A back in the 1950s. 13 A MCBs aren‘t particularly common in most countries but they do exist. Said oven is most likely to be connected to a 16 A circuit on the continent.
  10. R

    New pendant light turning off and on

    Are you sure the spotlights are mains voltage? I wouldn't consider it impossible that some 230 V LED lamps do strange things when connected to 12 V.
  11. R

    Old home electrics

    The chandelier sounds like it's a problem common to all three lamps, so check the wiring. With the wall light it could be lamp, lamp holder or wiring. Is that BC or ES/SES? If ES it could well be a loose centre contact. In that case turn off power at the consumer unit and carefully bend up the...
  12. R

    Flat / Slimline 3 pin plugs?

    A Schuko socket needs to be protected by a 16 A or smaller fuse or MCB though, as there’s no fuse in the plug. So assuming the current socket is on a 32 A ring the Schuko would need to be connected via an FCU.
  13. R

    Old home electrics

    True. My girlfriend had several Philips LED lamps that flickered for quite some time until they failed completely.
  14. R

    Flat / Slimline 3 pin plugs?

    The lead is unlikely to be more than 3x0.75, which means the biggest fuse you can use is 5 A.
  15. R

    Old home electrics

    Could be loose connections, possibly at one of the ceiling roses (from where the other light is fed).
  16. R

    Resistance test on cores of buried cable (Ed.)

    8 AWG is 8.37 mm2. Canada and the US have somewhat similar electric regs and as far as I know none of them require proper testing and inspection, therefore few electricians actually own testers.
  17. R

    5 Wires For Bosch Induction Hob??

    Hobs are usually a lot more powerful than ovens.
  18. R

    5 Wires For Bosch Induction Hob??

    Make is Bosch, model is unknown though.
  19. R

    5 Wires For Bosch Induction Hob??

    Very few hobs are actually three-phase. Most can be wired to run on either single phase or two phases of a three-phase supply.
Back
Top