  1. P

    Timer on a Santon PremierPlus Unvented tank

    Hi The tank is a PP300B, the stat is built into it. There doesn’t appear to be any wiring centre for the tank itself, the cable goes downstairs, into a wiring centre for the whole system, where it links to the zone valve and pump. To be honest even getting involved in the wiring centre...
  2. P

    Boiler firing constantly for hot watere

    I have been checking it manually, usually around 25-30% modulation when the hot water is on
  3. P

    Boiler firing constantly for hot watere

    Hi, I have one coming for the flow today, but it’s definitely the cylinder firing it, the heating is off and it’s the hot water circuit coming on. It’s a greenstar8000 35kw system boiler, set to 65. Ta Paul
  4. P

    Timer on a Santon PremierPlus Unvented tank

    Ok great, thank you for this, least I know what the next step is!
  5. P

    Timer on a Santon PremierPlus Unvented tank

    Thanks, so I do seem to have a permanent live and neutral coming from downstairs, the neutral is just connected straight to the tank, the live has a simple mechanical switch in between. So when I connect the neostat hw or even a cheap timer, I have the live from downstairs coming in, neutral...
  6. P

    Timer on a Santon PremierPlus Unvented tank

    Thanks. So I want a timer as currently the tank calls for heat every hour basically, even if no water is used. I am currently narrowing down why that may be (the tank doesn’t really seem to be losing any temp over several hours with some tests I have done, but must be enough to drop the...
  7. P

    Boiler firing constantly for hot watere

    Yea seems not! I will see about putting in another zone valve to rule out that issue and see from there. Thanks all
  8. P

    Boiler firing constantly for hot watere

    Yea so I don’t appear to have a seperate one for the immersion , just one stat for all…
  9. P

    Boiler firing constantly for hot watere

    Hi Yep it’s pretty much every hour. I did record the gas meter after you mentioned it before, problem is the CH comes on around 5am so I am not able to check it before that so I get the CH mixed in as well. It takes around 10 mins for the boiler to come up to temp from pretty much cold, then I...
  10. P

    Timer on a Santon PremierPlus Unvented tank

    Thanks for the replies, so currently I just have a live/neutral/earth from the boiler stat, it goes to a simple on/off switch beside it so I can isolate it. When this is on, it completes the circuit to the zone valve and pump downstairs, but these don’t fire until the thermostat on the cylinder...
  11. P

    Boiler firing constantly for hot watere

    So I left the power to the tank off all night, around 8 hours. I moved the thermostat to see where it clicked before I turned it back on, still seemed to be sitting around 4, so it didn’t think it had lost 10 degrees or anything. When I turned it on, it only called for hot water for 15mins (I.e...
  12. P

    Boiler firing constantly for hot watere

    Yea so it’s firing every 60/90 mins it seems, mostly every 60 mins almost right on the nose. It’s a 300L tank, so that would be even higher then? Is there any way to equate that to how much water I would be “losing” to cause that?
  13. P

    Boiler firing constantly for hot watere

    Good question, the setup came with the house, so I have just been trying to understand it all and I think that’s the next logical step! The part I don’t understand however is if I isolate the tank, it doesn’t lose anything and the stat doesn’t fire the boiler, so I must be seeing some water...
  14. P

    Boiler firing constantly for hot watere

    Yea, it does seem a bit OTT but can only go on what they have said, if it is larger then it’s a bit more worrying as I would need to be losing a decent bit of water every hour to cause the temp to drop that much. I have verified the tank seems ok and will hold the heat ok. My flow temp at the...
  15. P

    Boiler firing constantly for hot watere

    thanks! I spoke to santon/back who said that as soon as the tank drops 1 degree it will call for heat, which isn’t ideal, but I still must be losing water somewhere to cause it to drop….the mystery continues! My plumber has said we can put a flow meter on the hot water, see if we are losing any...
  16. P

    Timer on a Santon PremierPlus Unvented tank

    Hi I have been unsuccessfully along with my electrician trying to add a timer to this unit for the thermostat. When connected via a simple on/off switch it’s fine, but the minute I put any type of other switch in front of it, the switch goes bonkers as soon as the thermostat clicks on. I have...
  17. P

    Boiler firing constantly for hot watere

    So currently it fires every hour to top itself up, however when it was isolated it didnt call once over a 6/7hr period, so I know the tank xcan hold the heat. So I am just trying to understand if when the tank isnt isolated (i.e flow is open, but no taps/showers on) I cshould expect it to hold...
  18. P

    Boiler firing constantly for hot watere

    Hi, sorry do you mean shut the incoming cold feed to the cylinder? Paul
  19. P

    Boiler firing constantly for hot watere

    Hi, yep, I turned off the valve on the flow after the cylinder so no water could leave it, this way the tank kept temp and didnt call for heat over a 6/7hr period. Soon as I opened it again, it was back to normal, every hour or so. When it calls overnight, all the taps/showers etc are off, and...
  20. P

    Boiler firing constantly for hot watere

    So this didn’t make any difference. So I am not going down a rabbit hole, the tank when isolated holds temp without firing the boiler for 6/7 hrs. So should I expect at least 3/4hrs when the tank isn’t isolated, but all hot water circuits are closed? If so it would indicate something is slowly...