    Issue with Radiator connected with 8mm Piping to existing 15mm Copper

    Hello I am using Weather Compensation so the Flow and Return Temperatures fluctuate. Thanks Kevin
  2. K

    Issue with Radiator connected with 8mm Piping to existing 15mm Copper

    Hello Agile I am aware of that hence why I purchased a Differential Thermometer. I managed to achieve an 11⁰C Drop, give or take a Degree across each Radiator, except for the Living Room Radiator as I was unable to get a reliable Temperature Reading. Thanks Kevin
  3. K

    Issue with Radiator connected with 8mm Piping to existing 15mm Copper

    Hello Thanks for the Replies and apologies for not Replying sooner, I have been dealing with some things. I decided to check the Balancing for myself, I have never done it before so researched it as much as I could prior to trying it. First of all I checked to see how much the Lockshield...
  4. K

    Issue with Radiator connected with 8mm Piping to existing 15mm Copper

    Hello Thanks for the Reply. The Radiator was Sized by the Heating Engineer and was intentionally Oversized. The Radiator is a Type 21 at 1000m x 600mm and Rated at 1345 Watts (1121 Watts was recommended by the Radiator Calculator) The Room is 3.9m x 3.0m, Two Exterior Walls and New UPVC...
  5. K

    Issue with Radiator connected with 8mm Piping to existing 15mm Copper

    Hello all I have an issue with One Radiator that I hope you can offer some advise on. I had a Type 11, 1000mm x 600mm Radiator Installed in the Living Room which had no Radiator prior, in 2018. Even though the Radiator got Hot it never sufficiently Heated the Room. In 2022, I had the...
  6. K

    Vaillant EcoTec Sustain 28, sensoComfort RF and sensoNET

    Hello The P+ refers to the Radiator Type, 2 Panel one Set of Fins. I do not understand why the Boiler is not Cycling more frequently, all I can tell you is what I see, sorry. Thanks Kevin
  7. K

    Vaillant EcoTec Sustain 28, sensoComfort RF and sensoNET

    Hello Sorry, when i said that the Boiler was not continually Cycling I meant that it does Cycle but not all the Time, hopefully that makes sense. Also, the ecoTec Sustain is 28kw but has 19kw for Heating. Thanks Kevin
  8. K

    Vaillant EcoTec Sustain 28, sensoComfort RF and sensoNET

    Hello Sorry, I misunderstood. I have the Wireless Weather Sensor connected to the sensoComfort which Reports the Outside Temperature as being 11.5⁰C. The Current Flow Temperature is 40⁰C (ish). All of the Rooms except one are upto Temperature (20⁰C) after approximately 4.5 Hours...
  9. K

    Vaillant EcoTec Sustain 28, sensoComfort RF and sensoNET

    Hello Thanks for the Replies. The Boiler does not Cycle continuously and works well, thankfully. With the sensoComfort Adaptive Heat Curve Enabled, do you happen to know if there is a Learning Period? The sensoComfort was only Installed Yesterday Afternoon so I am assuming that there may be...
  10. K

    Vaillant EcoTec Sustain 28, sensoComfort RF and sensoNET

    Hello all Well, everything is Installed and Working as it should. Regarding the Heat Curve, it is currently Set at 1.2 which picked up during Installation and the House is Slow getting to Temperature. The Adaptive Heat Curve is Enabled. Does anyone know how long it takes for the Adaptive...
  11. K

    Vaillant EcoTec Sustain 28, sensoComfort RF and sensoNET

    Hello all I hope you are well. I had a Vaillant EcoTec Sustain 28 Installed in January 2022 under the Eco Scheme. I only had a Choice of Manufacturer, I chose Vaillant, however, I did not have any say in the Model or Kw Rating of the Boiler, that was left to the Eco Scheme and the Installers...