  1. D

    Oil Burner Nozzles

    OK, I was getting that impression; though I'm still curious as to why they would make two types that are exactly the same. No. I'm just replacing a partially blocked nozzle with a new one. I'm not intending to make any other adjustments, so the combustions levels shouldn't change. When it...
  2. D

    Oil Burner Nozzles

    Yes WDIK, I saw that, but that just confirms that H and EH have the same 'hollow' spray pattern; it doesn't say what the difference between H and EH is. However, the product range page says that the EH range are "Special nozzles for oil burners used on kerosene", but does say what makes them...
  3. D

    Oil Burner Nozzles

    I ordered a couple of replacement nozzles recently for my Sterling 40 oil burner. I asked for Danfoss 0.65 80EH but was sent 0.65 80H. When challenged to resend me the right ones, the supplier has tried to assure me that the H type are interchangeable with the EH type - so no problem. Or is...
  4. D

    Oil burner locks out after running for a few minutes

    OK, so here's the end of the story... I hope. I tested the resistance of the coil just after the burner had shut down, and (just as predicted) it was open circuit. Had to wait a while for a replacement coil ('overnight' delivery by FedEx took three days!) but it was only a five...
  5. D

    Oil burner locks out after running for a few minutes

    Wow, quite a flurry of activity over the past few hours!... I'll definitely try testing the resistance of the coil tonight, but I've stuck my neck out and order a replacement anyway. If it turns out to be the pump, at least I'll have a spare coil if it fails later in life. Just an aside -...
  6. D

    Oil burner locks out after running for a few minutes

    OK, so thanks to the suggestions posted earlier, I connected test leads to the valve solenoid circuit. At startup, current flowed to the solenoid, the valve opened and burned for 4 minutes. Then the flame went out and the valve was switched off ... the two things happened almost at the same...
  7. D

    Oil burner locks out after running for a few minutes

    Thanks for your comments oilman. I guess fitting a new coil on the value is the only way I'm going to know if it's this that's causing the problem or not. :roll: Any other advice on isolating the problem would be appreciated. The boiler itself has given pretty good service since it was...
  8. D

    Oil burner locks out after running for a few minutes

    Thanks for the quick responses! The burner is only running for a couple of minutes, so nothing has much chance of getting warm - the external wiring to the solenoid valve is definitely still cold when the burner goes out. However, your suggestions has made me think there could be...
  9. D

    Oil burner locks out after running for a few minutes

    Background: HCC Thermotronic T2 oil-fired condensing boiler, that uses a Sterling 40 burner, which is fitted with a Danfoss BFP11 pump. Fault: When first switched on, the burner fires up and runs normally for about 4 minutes. Then the flame goes out, and the burner locks-out after a few...