  1. S

    Underfloor heating not working

    Many thanks for assistance. Replaced blending valve and we're away. It seems the old valve was a TMV 2 limited to 48 degrees so was not getting warm enough anyway apart from it being full of crap!
  2. S

    Underfloor heating not working

    Thanks for the enlightenment. Electrics operate ok. stats call for heat, they open two port and pump starts to operate. So I guess this only leaves the blending valve as the culprit.
  3. S

    Underfloor heating not working

    Hi All Went to see customer with an UFH problem. Pump not working so replaced, but still no heat! Have heat to manifold via open 2 port motorised valve. Heat starts to enter UFH pipes but does not flow through to return manifold. System has 2 auto air vents but cannot get any air out. Have...
  4. S

    Sterling Burner lockout

    Thanks for the feedback guy's. The problem was the coil on the Sterling burner. Have emailed EOGB and Riello regarding courses. That should get me started. Once again many thanks.
  5. S

    Sterling Burner lockout

    Hi Oilman A friend went on one of these courses and gave me a bad report so have given them a wide berth up to now. Is there one in particular you could suggest?
  6. S

    Sterling Burner lockout

    Thanks for the quick response guys. I will check continuity when lockout occurs. I assume my standard multi meter will do this ok. I am letting this one wind me up a bit!! You always get one now and again.
  7. S

    Sterling Burner lockout

    Hi guys. I am having a problem with this one. Burner consistently locks out after 12 - 20 minutes of use. Have given the unit a standard service, changed nozzle, cleaned all oil filters including pump and baffles etc. Have checked oil line for leaks. I had a spare control box and photocell in...
  8. S

    Selectos D42 oil burner parts

    Thanks for all these gold nuggets!! Wish I had joined earlier! Hope I can have some input in the future! :D
  9. S

    Selectos D42 oil burner parts

    Thanks for that. There is light at the end of the tunnel! :)
  10. S

    Selectos D42 oil burner parts

    Hi Guys Anyone know where I can get spares for this oil burner. Specifically electrodes, leads and transormer. A manual would be good too but I guess i'm pushing my luck after all the burner is 40 years old I think. Cheers :(