    I have a 15 year old Miele Premier 520 which just starting making an unusual noise 2 mins before the end of the high speed spin cycle. Now, when stationary with no clothes in it, when I manually rotate the drum it makes a squeaking sound (both directions). I tried lifting the drum and it's not...
  2. L

    37v present in switched off lighting circuit!

    I just realised I never posted the upshot of this -- I got an electrician in who did put in an earth between the breaker box and the master supply. The 37v problem was finally traced to a miswire in the double pole switching units in for the lights -- though not sure exactly why this caused it...
  3. L

    37v present in switched off lighting circuit!

    gulp! I guess I should get it checked, though I remembered I had a full structural survey including an NICEIC report back in 96 before I bought the house; I looked it up and has "TN-S" ticked. But re-reading it now, I notice it suggest a full re-check after the recommended rewire, so maybe...
  4. L

    37v present in switched off lighting circuit!

    Just two heavy duty wires from breaker box to the meter as depicted 2 posts above. (wire on the left of these two just goes to bell transformer) You can see two green/yellow going upwards from the breaker box; one goes to the gas pipe, and one up into the garage ceiling.
  5. L

    37v present in switched off lighting circuit!

    Here's the circuit breaker: Is that what you want? The two righthand large cables at the bottom go to the meter (see earlier picture)
  6. L

    37v present in switched off lighting circuit!

    thanks for this. I'll stop worrying :-) PS Here's a closeup of the two clamps:
  7. Untitled

    Untitled

  8. L

    37v present in switched off lighting circuit!

    ... hmm... actually it may be TNCS, but unlabelled (no safety sticker on the gas bond either). See: though I was expecting the earth to neutral connection to be done at fusebox, not the other side of the meter.
  9. Untitled

    Untitled

  10. Untitled

    Untitled

  11. fusebox

    fusebox

  12. L

    37v present in switched off lighting circuit!

    Thanks for this. No sticker on the main circuit breaker box, so presumably not TNCS; Of the green/yellow wires leaving the breaker box, one goes to the gas pipe, the other goes up to the garage ceiling, and then I know not where! In any case, back to the original topic of the post, it sounds...
  13. L

    37v present in switched off lighting circuit!

    I checked: all earths are connected together within the switch boxes. I assume that the earth from the distribution box is connected to actual earth! (Though this is a 1997 installation so, as I understand, there was then no need for an actual electrode into the ground; I can see a bond to the...
  14. L

    37v present in switched off lighting circuit!

    Yes I am; I spent a long time wondering which ones to get and whether they would be bright enough. (I didn't want spend as much as the new ones costing around £20 each). I originally had 8x60w incandescent. Now I have 12x4w led and they are at least as bright. Slightly pinker in tinge. The ones...
  15. L

    37v present in switched off lighting circuit!

    Thanks for this; will check tomorrow once it's light. It was an electrician whom I contracted via the builder who was doing some internal renovations at the time, and having just bought the house and having had a full structural survey recommending a rewire, that's what I did. I confess I...
  16. L

    37v present in switched off lighting circuit!

    They were originally controlled by 2-way switches; but in late 90s I fitted a dimmer switch, so rewired one of the switches so both-ways on and put the dimmer switch on the other one. When I fitted the leds, I had to remove the dimmer switch of course and put back a regular switch, but all the...
  17. L

    37v present in switched off lighting circuit!

    My house was professionally rewired in 1997. I recently replaced 8 individual kitchen R60 spots (2 circuits) with 4 sets of 3xGU10 spots. These came with halogen and all worked as expected. I recently replaced these with LED spots, and in one circuit I notice that the leds are still (very dimly)...