    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Thanks oilhead. Replaced the vessel and things did improve, but still seem to have water flow through the heatstore/plate exchanger when CH is in demand. Once again pipes either side of the pump are only warm not hot so diverter valve can be ruled out. Think I have sussed it though looking at...
  2. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Thanks for the info oilhead. Plumbarena are doing alright out of me ☺ BTW does the new vessel come charged to 1 bar with nitrogen?
  3. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    I'm back with an update after taking another look today at the boiler. Decided to drain the system after a flush then to look at the expansion vessel (big red thing on right). Once the system was drained I pressed on the valve on the top of the expansion vessel and rather than 1 bar of...
  4. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    I get the same behaviour so 3 the burner stays on permenantly with only 1 I would say where the burner cuts out and pump stays running..
  5. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    So when the heating is working and the CH pipe out is hot the return is hot. When the CH is lukewarm the return pipe is only warm and basically the pipe at the back of the boiler marked 'rear of appliance' with an arrow pointing to the back of the boiler gets very hot. I think the heat/water...
  6. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    If the CH thermostat is set to 1 then the burner is off for a minute or so but we have it at 3 so the burner is normally staying on. When I opened the 3 way it was mucky inside but not sludgy and the ball was intact and still attached. The system is clean but maybe there is something lose in...
  7. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    We have similar vintage oil burners Heat store heating lasts about 8 minutes and moving HW stat up and down switches boiler on and off during that time. The startup procedure for the CH from room stat triggering is fan, burner then pump so guess 3 way is triggered same time as fan then micro...
  8. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    I won't tell you how much googling I've done on this ☺ I've unscrewed the cap and can see the pump spinning, have put a screw driver in to confirm and this morning held a screwdriver on the pump case and other end to my ear to hear rotation. The water heating is fine, but the random no flow of...
  9. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Thanks for the responses John. I only got air out of the middle right side one so the combustion chamber one. I had the pressure at just above 1 bar and did try it at 2 to see if any air shifted. I've gone round the 9 radiators to check for air and nothing.
  10. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    I've bled the pump, manually the heat tank auto vent (to confirm it still works). The ones on top of the boiler are the three in the piccy. Cheers
  11. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Thought i'd connect up my meter to the pump today so these were the voltages and noted behaviour. Heating luke warm no flow = 240/241v Hot water only = 243/244v Heating working fine = 242/243v
  12. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Dry pump test went OK and no problems with the running of that. Random behaviour persists though with heating circulation to the radiators. I manually held the 3 way valve so the hot water circuit was closed but still the pipes either side of the pump were cold with the pipe at the back of the...
  13. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Thanks for sticking with me on this oilman. I unscrewed the cap on the heat store so the autovent expelled air and I also undid slightly the silver cap on the pump again to let air out. Couple of things I want to look at today. I was going to get a meter on the pump cable to see voltage...
  14. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Not checked the PCB outputs but have an update. Called WB technical and explained the full problem to the guy on the other end and after a confirmation of the boiler he said it's a diverter issue. As I've already changed the head and internal ball valve/spindle I decided to replace the valve...
  15. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Its doing it when the hot water isnt in demand and when the heat store isnt being heated. Hopefully i will get something out of the phone call to WB technical line.
  16. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Spoke too soon. We seem to be back to random hot radiators, hot radiators at first then go warm before room stat switches off boiler or radiators just getting warm. Looking at the pipe at the rear of the heatslave boiler labelled 'rear of appliance' this gets very hot when the heating is on...
  17. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    New diverter arrived today so went to work on the boiler. Couldnt get complete valve out of boiler so replaced the head and the top plate that contains the rubber ball. Not sure the one i took out was origional or not as was a square plate rather than the new curvy one. Rubber ball looked...
  18. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Thanks for the info oilman. I've ordered a new complete 3 way valve so will update once installed with the results and a pic of the internals of the old one should there be something obvious.
  19. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    Thanks for the reply. The diverter is a 3 way Honeywell model v4044f1125. I have the pump speed up at 3. I did a test so turned down boiler temp so when it triggered it started up and I could hear the 3 way valve operate. It did operate very slowly from the default water to the heating. I did...
  20. S

    Worcester Bosch Heatslave 15/19 Lukewarm Radiators

    If anyone can give me pointers it would be much appreciated. I've done loads of googling but yet to find any clues apart from 3 way valve. I have a 15 year old Worcester Bosch Heatslave boiler that has been working fine until recently. Hot water not an issue, but 8 times out of 10 when the...