  1. G

    Testing a 3 port valve.

    Boiler seems to be fired up now ?
  2. G

    Testing a 3 port valve.

    The boiler initially started up but has now gone off? The cylinder is cold ? Thanks
  3. G

    Testing a 3 port valve.

    Right I've taken controller from wall so backplate is exposed and linked live to hw on ?
  4. G

    Testing a 3 port valve.

    Hi everybody sorry I had to go away with work.I have multi meter in hand, so to check the cylinder stat?
  5. G

    Testing a 3 port valve.

    Thanks yes I have a multi meter, I will check tomorrow and report back many thanks for all your help
  6. G

    Testing a 3 port valve.

    Hi many thanks a stat seems the cheaper option to try?
  7. G

    Testing a 3 port valve.

    Yes both was on at the controller, I then turned stat up and down you could hear the click of the stat but nothing from 3 port valve?
  8. G

    Testing a 3 port valve.

    Ok I turned on both together hot water and heating and nothing seemed to make ve?
  9. G

    Testing a 3 port valve.

    I put heating and hot water on, then turned cylinder stat up and down and nothing moved in the 3 port valve?
  10. G

    Testing a 3 port valve.

    Heating is on and lever is loose
  11. G

    Testing a 3 port valve.

    Hi I do have an immersion heater fitted but it's on a 30 min/1 hour/2hour switch which is a bit of a pain in the morning as can not be programmed.
  12. G

    Testing a 3 port valve.

    Hi thanks, I have hot water only on the programmer and the radiators are not getting hot
  13. G

    Testing a 3 port valve.

    Hi thanks yes the lever has resistance you can hear the whirl sound when pushed. The central heating is working too.
  14. G

    Testing a 3 port valve.

    4073A thanks
  15. G

    Testing a 3 port valve.

    Hi it's a Honeywell thanks
  16. G

    Testing a 3 port valve.

    Hi My hot water has gone on the blink, I can get central heating but no hot water? It's a normal boiler, gravity fed system with a Honeywell 3 port valve. I assume it's the valve that's gone but how can I make sure? I have turned hot water on with the wall mounted controller and you can hear...
  17. G

    Any good problem solvers out there?

    I think I've sorted it! I bought a new pump £400 a negative head one. Fitted it and it was just the same! So I followed the pipe work from the pump and it goes through the ceiling into the attic and there was a NRV. So I removed that and it works! So £400 wasted on a new pump....damn
  18. G

    Any good problem solvers out there?

    Thanks everybody I will inform you what happens..
  19. G

    Any good problem solvers out there?

    Ive ordered a new pump an universal head one a Salamander RP100TU, I will have to sell the other pump on eBay!
  20. G

    Any good problem solvers out there?

    I did phone Salamander and played them the noise down the phone, the bloke said he has worked for them for 12 years and hes never heard anything like it !