  1. ManxMax

    Trianco Combi 70 Weirdness

    Can't get anyone to service it here on the Isle of Man - heating engineers are not interested unless they installed it or you need a new installation. Serviced it myself last autumn - oil pressure was fine, but I don't have equipment to do a CO2 test. Wondering if it might be a dirty photocell...
  2. ManxMax

    Trianco Combi 70 Weirdness

    Hi all Wonder if anyone has an idea of what is going on with my eccentric Trianco oil boiler - which would have never worked at all if it hadn't been for the help I received on this forum. Thanks to those concerned. Anyway, the thing used to trip the little button under the control box at...
  3. ManxMax

    Which Stat is Duff?

    Thanks Tony, I'll give it a go. Cheers
  4. ManxMax

    Which Stat is Duff?

    Hello Chaps I have a Trianco Eurostar Combi 70 that was a so-and-so to get sorted last year (thanks to all that helped with advice on that), but I now have a problem with the Boiler Limit Stat cutting in after a few minutes and I have to wait for 10-20 minutes before I can press the button...
  5. ManxMax

    Boiler Limit Stat help needed..

    Thanks John sounds like a good theory, I'll check it out. Max
  6. ManxMax

    Boiler Limit Stat help needed..

    Hi Chaps, I finally managed to get my old Trianco Eurostar combi 70 going, but a least once a day the boiler limit stat shuts it down and the button on it has to be pressed. Does the stat need replacing of is something else causing it to trip? Also, anyone know why the DHW doesn't work...
  7. ManxMax

    Trianco Eurostar Nightmare - Help!

    Yes John, the combustion chamber was sooted up. The mixture is set correctly now and running clean. The Trianco manual says a pressure of 130psi but the tech guys at Riello say 8 bar, which, as you know is more like 125psi, coupled with the dubious quality of Manx Petroleum's kerosene and not...
  8. ManxMax

    Trianco Eurostar Nightmare - Help!

    Well then, after replacing almost everything (I even borrowed a control box). The so-and-so still wouldn't work. So, as a last ditch attempt, I stripped down the burner, cleaned everything (again). Noticed there was some soot in the box. Hmm? Could it be that it built up when it was running for...
  9. ManxMax

    Trianco Eurostar Nightmare - Help!

    I like your style John! I'll give that a go. If nothing else, sounds like my kind of fun! Makes sense too! Thanks Max :D :D
  10. ManxMax

    Trianco Eurostar Nightmare - Help!

    Hi Mandate There is evidence that oil is being discharged from the nozzle. As for a spark, with the burner cover off I can see a flash from down the back of the control box coming from up the business end (accompanied with a cloud of dirty smoke every time it tries to start (cough!)...
  11. ManxMax

    Trianco Eurostar Nightmare - Help!

    Thanks for your input John. Baffles were all clean and correct, but I will re do them again as it ran for a week after before this problem occurred so is probably mucky again now. Didn't get a flue analysis done when it ran as I can't find anyone to do it! This Island's a lovely place to...
  12. ManxMax

    Trianco Eurostar Nightmare - Help!

    Finally got the beast to run and was working fine for a week. Last Saturday morning had a lockout. Reset and... no joy. The burner starts and tries to make a flame. Pulled out the burner, cleaned everything, including photocell, reset electrodes, checked fuel flow (fine) back together and it did...
  13. ManxMax

    Trianco Eurostar Combi 70 - 3 Port Pump Confusion???

    Thanks Oilhead - will do. I still don't understand how the DHW can work if the CH has the flow through the pump. Can anyone enliughten me? Cheers
  14. ManxMax

    Trianco Eurostar Combi 70 - 3 Port Pump Confusion???

    Hello Folks Finally have my old Eurostar Combi 70 running (oil pressure gauge helped!) but have now discovered that the DHW is not hot when the CH in running. Turn off CH and plenty of hot water. Checking the the electrical connections to the 3 port pump I found that there was 230v on the...
  15. ManxMax

    Trianco Eurostar burns but no heat/hot water

    Thanks for the advice. I'll check the pump setting. Cheers.
  16. ManxMax

    Trianco Eurostar burns but no heat/hot water

    I thought about bypassing the boiler stat just to check, so I'll give that a go tomorrow (it does click at the lowest position). There is currently no room stat, although the manual says that the connections for one should be crossed if not required, so I'll check that out even though the...
  17. ManxMax

    Trianco Eurostar burns but no heat/hot water

    Chapter 2... Pump stripped, all in order, rebuilt and refitted. Took the opportunity to tidy-up some dreadful plumbing (not sure if it was factory stuff) and replace the CH in/out shut-off valves. Anyway, turned the beast on and waited. Nothing, other than the pump cam on as soon as I...
  18. ManxMax

    Trianco Eurostar burns but no heat/hot water

    Thanks John, good call. Yep, IOM is a great place to live (unless you want a heating engineer!)
  19. ManxMax

    Trianco Eurostar burns but no heat/hot water

    Thanks. I'll strip the pump. I can hear it whirring away, but the impeller could be trashed, I suppose. Also, the body of the pump is getting v.hot. PS. anyone know what the factory setting should be on the oil pressure screw and airscrew. I can't get an engineer to look at it, here on Craggy...
  20. ManxMax

    Trianco Combi 70 baffles

    Anyone know what is the correct arrangement of these? Currently cups facing up with a plate on the top ones and three a side in the flue box. Ta.