    Dynamic pressure drop at outside tap

    Hi Tony I've measured the flow through internal stop cock every 0.3 bar or so, adjusting the flow from the outside tap to give the desired dynamic pressure. I get: Pressure [bar] Flow [ltr/min] 3.0, 0.0 2.7, 5.1 2.4, 6.0 2.0...
  2. B

    Dynamic pressure drop at outside tap

    Hi guys My newly built house is connected to the water main by about 30m of 32mm o/d MDPE pipe (roughtly 26mm i/d). At the outside tap near the stop cock, the measured static pressure is a shade over 3bar. If I leave the gauage on the outside tap and turn on an indoor tap my dynamic...
  3. B

    DHW Cylinder Expansion Vessel Pre-Charge

    Sorry for the confusion - I always thought PRV was Pressure Reducing Valve
  4. B

    DHW Cylinder Expansion Vessel Pre-Charge

    Hi steelmasons No typo. The tank is a Danfoss DWH-300. It comes with a 24 litre expansion vessel. The spec is (typed from the datasheet) Max water supply pressure 10 bar Pressure reducing valve 3 bar Expansion valve 6 bar Expansion vessel charge pressure 3bar Operating pressure 5.5 bar...
  5. B

    DHW Cylinder Expansion Vessel Pre-Charge

    Hi guys I have a quick question regarding the correct pre-charge pressure for an expansion vessel (24 ltr) on the cold supply of a DHW cylinder (300 ltr). As measured after a combined 3 bar PRV + 6 bar safety relief valve assembly, the static pressure of the cold supply is 2.5 bar. The...