Search results

  1. M

    Voltage drop

    I know, but the 5% is applied to the middle, end or evenly spaced apart as an algebraic sum?
  2. M

    Voltage drop

    But do I assume a full 20amps of load lumped at one end?
  3. M

    Voltage drop

    I did find this: http://cablesizer.com/iec/
  4. M

    Voltage drop

    This is a 20amp radial in 2.5mm2 T&E. My apologies for not stating it earlier.
  5. M

    Voltage drop

    The regs say no more then 5% voltage drop, however how do I apply (calculate) this for socket circuits?
  6. M

    Cross sectional area current capacity

    OK, doing more research I came across this, not sure if it helps though, the tables used for countries that use 2.08mm2 wire. But it has me confused. At 75*C, 2.08 is listed at 20amps. I take it the conductor insulation is rated higher...
  7. M

    Cross sectional area current capacity

    That makes sense. Now my understanding is the factor is less restrictive for 1.5mm2 because smaller conductors can dissipate heat better? Or is it the other way around? Correct to think that heat dissipation of 2.08mm2 is in between 1.5mm2 and 2.5mm2? Edit: just to confirm, by 1.35 you mean...
  8. M

    Cross sectional area current capacity

    Thanks! That is what I was looking for. :) I think it does hold some value in my opinion. However this equation only works for clipped direct I take it? What would it be reduced to when using other methods like method A? And the power curve is based on a 70*C conductor operating temperature?
  9. M

    Cross sectional area current capacity

    Multi core. Live and neutral plus PE in conduit (3 conductors total).
  10. M

    Cross sectional area current capacity

    I dont think so. I did some digging and found this. 12 gauge is 3.31 mm2. This wire here is 2.08mm2.
  11. M

    Cross sectional area current capacity

    I dont think those are accurate, or would comply with the regs. For example 2.08 seems to be listed at 15 amps, but that is obviously based on method 101 as 1.5 is already 15 amps for installation method A. Dont the regs base the values off a certain equation? Either that use the current value...
  12. M

    Cross sectional area current capacity

    How would one determine the current carrying capacity of 2.08mm2 conductor?
  13. M

    Earth fault loop impedance 3x230 nett

    How do earth fault loop impedance requirements and disconnect times change when the live to earth voltage is 133 instead of 230? Thanks!
  14. M

    Start Relay/Overload Wiring for Fridge/Freezer

    Do you have a wiring diagram for the unit? That usually has detailed info.
  15. M

    Twin and Earth

    Is it assumed that a 60*C conductor temperature for example will produce a 60*c temperature at the terminals? Or they run hotter?
  16. M

    Twin and Earth

    But what are the connectors and MCB terminals rated for themselves? Or they play no role in wire selection?
  17. M

    Twin and Earth

    70*c for the conductors, at least all adjustments put together will prevent the temperature going any higher. got it :) Earth fault loop impedance calcs assume 70*C Live and PE? As for the terminations, must they also be rated 70*C? Or are they typically lower?
  18. M

    Twin and Earth

    Brilliant! :D
  19. M

    Twin and Earth

    Ok, my mistake, I did not know it was that old. The values for MCB seem to change insulation method, but I have been told they are "good rules of thumb" I have to ask, with Twin and earth, what is the temperature rating of the individual PVC insulation on the conductors? Does it vary or a...
Back
Top