    Main boiler turning on and off despite reaching room stat temp

    Thank you for all your help. Electrician booked
  2. L

    Main boiler turning on and off despite reaching room stat temp

    Thanks for the information. I have drawn a diagram of wires in my cupboard where the valve, pump, cyl stat is. I have two cables coming in One cable with 2 blacks, 1 G/Y, 1 Brown, 1 Blue One cable with 1 red and 1 black. I can trace them so far as seen on my diagram. The red cable coming in...
  3. L

    Main boiler turning on and off despite reaching room stat temp

    Thank you to everyone who has posted on here. It's all much clearer and guess the issue is whether I invest in a new boiler? Old maybe less economical boiler for next 10 years or replace at a cost with much more efficient and modern way of operating!! Any suggestions on what would be a good...
  4. L

    Main boiler turning on and off despite reaching room stat temp

    I have taken a look at front of boiler. The temperate dial is as far clockwise as it can go. I assume this means the temperature the boiler can create is high or as high as it can go. Is there any merit in turning this down? Will this allow the boiler to stay on longer pushing heat to the...
  5. L

    Main boiler turning on and off despite reaching room stat temp

    I will check out the temperature setting - thanks for suggesting All radiators get hot, they were balanced by CH engineer after some of them were not getting hot, so I'm happy with that being set correctly. The radiators seem to remain hot throughout as the boiler is as quoted switching on and off.
  6. L

    Main boiler turning on and off despite reaching room stat temp

    Thankyou for your reply Today I made a note of times and temp 7am - boiler has been off overnight and not fired up. Boiler off - room temp 17'C Room Stat increased to 20'C Boiler on for 20 minutes - temp reached before it turns off 18.5'C ( would this indicate that boiler stat has reached its...
  7. L

    Main boiler turning on and off despite reaching room stat temp

    I have a Main boiler ( installation paperwork states Baxi Potterton solo 15HE ) however it looks similar bar the logo on the front. Does this boiler have an internal thermostat? if so, I guess this could be the reason my room stat isn't reaching the required temperature at first before the...
  8. L

    Replace silver flexi hose on expansion vessel

    I've decided to leave it all alone. The silver flexi hose isn't something I could buy off the shelf. Would need to wait until Monday when plumb centre shops open. My system is serviced once a year and they just did it Wednesday last week. So I'm calling them back to buy the flexi hose and...
  9. L

    Replace silver flexi hose on expansion vessel

    I noticed water coming out of a light socket on floor below where water tank and expansion vessels are. Looking in the cupboard it was obvious to see the silver flexi hose that connects one of two expansion vessels was leaking and judging by the amount of water on the floor it had for a day or...