    Ch heats to 27, then stops, Ecotec

    HI, Update: the thing doesn't stay on. Once it climbed to the required 58 degrees, but thereafter keeps cutting in the mid-thirties and the flashing symbol arrives. Then it stay off, rebooting every now and again. No fault codes, either. Flummoxed. Any thoughts? Thanks in advance. Cheers, Paul
  2. P

    Ch heats to 27, then stops, Ecotec

    Hi, That's cured it, they were shut. The temp continued all the way to almost 70, then it cut and continued to gurgle all the way down to 19, then it kicked in again, this time rose as far as 55, then cut and gurgled for a while until it dropped again to 17, the hour glass flashing from mid...
  3. P

    Ch heats to 27, then stops, Ecotec

    Hi, Thanks, I'll nip down and check that they're open and have a look behind the insulation. The safety hangs above a bucket - I'm in Belgium! Cheers, Paul
  4. P

    Ch heats to 27, then stops, Ecotec

    Here's an image, which ones should be fully left? Thanks, Paul
  5. P

    Ch heats to 27, then stops, Ecotec

    Hi, Yes, I mess with it every time I leave the house for long periods, which I do twice a year. Are the valves open if they are full clockwise, to the right? Thanks for your input. Cheers, Paul
  6. P

    Ch heats to 27, then stops, Ecotec

    Hi All, I've searched and checked the FAQs, but can't find the answer, sorry. By Ecotec pro heats the water fine, but when I set the ch temp to say, 65 it fire's up and move quickly from 17 to 21, 22 degrees, then move very slowly to 27 and the boiler stops. No fault code. Have I inadvertently...
  7. P

    Ecotec pro, no fault codes, ch, but no hot water

    Is it the flow sensor or the water pressure sensor, (smaller of the two), I need to pull out? Thanks
  8. P

    Ecotec pro, no fault codes, ch, but no hot water

    Hi, Thanks for the further comments. It does look as though it's the aqua sensor/flow turbine. One final question, please, if it is the sensor wouldn't it give a fault code, or wouldn't it register a fault? No other plumbing done. Would this be the part I need? VAI0020059717 Sensor VCW/VUW Part...
  9. P

    Ecotec pro, no fault codes, ch, but no hot water

    Hi, Just S31, though the little parasol isn't out and I'd not set the ch to off. Thanks again!
  10. P

    Ecotec pro, no fault codes, ch, but no hot water

    Took it out of summer mode, ch on and shows s04, nothing else when I scroll. Back to summer mode and s31, nothing when I scroll. Thanks
  11. P

    Ecotec pro, no fault codes, ch, but no hot water

    Hi, There is no 'I' button, there are the two + two buttons and the reset. The bottom pair, marked + and - indicate a ladder when pressed at the same time. When I do this the CH kicks-in until I press top left button - back. When I press reset I get a one second whirring. Thanks for helping.
  12. P

    Ecotec pro, no fault codes, ch, but no hot water

    Thanks for the helpful replies, much appreciated. I'm not sure how to get at the s codes, could anyone advise on this? There are no lights or symbols flashing when I turn the tap. The aqua sensor looks favourite at the moment Can the wheel be freed, or is it a new part? Thanks again, Paul
  13. P

    Ecotec pro, no fault codes, ch, but no hot water

    Hello All, I have searched this, but I can't get to the bottom of the problem. The pressure is fine and there are no fault codes CH works as normal, but when I turn on the hot tap it simply runs cold. Even with the boiler firing the heating and running the tap there's not even a hint of...