  1. M

    Bristan Bliss electric shower advice

    Thanks again Terry. Will get someone out to address the circuit.
  2. M

    Bristan Bliss electric shower advice

    Hi Terry, thanks for this. Sorry, I'm rubbish at stuff like this, but it's exactly this that is tripping - https://www.cef.co.uk/catalogue/products/1932097-32a-sp-1-module-6ka-type-b-30ma-rcbo
  3. M

    Bristan Bliss electric shower advice

    We've a Bristan Bliss 10.5kw electric shower, which has always tripped the electrics after roughly 10/15 minutes use. If we were to replace this with another Bristan Bliss, would a 9.5kw be ok? Or would we need to think about a 8.5kw? Cheers.
  4. M

    Briston shower problem

    Hello. Thanks for the reply. Do you mean a loose connection in the isolator or the shower itself?
  5. M

    Briston shower problem

    Hi all! Six months ago we had a Bristan Bliss 10.5kw shower installed. Over the last 48 hours it has developed a fault. After a few minutes running (time varies), the shower will stop working. At the moment when the shower stops, you can see the red light on the isolator switch flickering. The...