    Garage Fuse Box and Spur

    Thanks for the comments and questions. The CU in the house has two RCD's but neither are associated with the garage MCB. The house CU is wired, ¦Main Switch ¦ Garage MCB B20 ¦ 80A RCD ¦ (rest of house MCB's)¦. When the house CU was upgraded 8 years ago I remember him saying now that he'd leave...
  2. D

    Garage Fuse Box and Spur

    **Update** The CU in the house only has a B20 MCB feeding the garage. There is no RCD to the garage. I'm assuming this is bad and is why the single socket that was in the garage is a metal clad RCD socket. Without and RCD in the circuit am I left with little choice but to swap out the garage...
  3. D

    Garage Fuse Box and Spur

    Thanks EFLImpudence. I'll go for just adding the sockets then. I don't mind the metal fuse box, it performs the same as removing it I guess.
  4. D

    Garage Fuse Box and Spur

    Hi, My garage has a metal Wylex fuse box with two fuses. Wire fuses are 20A for the socket and 5A for the lighting. The house CU was replaced 8 years ago and the installed a 20A MCB for the feed. Ideally I'd like to replace the metal fuse box with a CU and then run a radial circuit of sockets...